                       Installation manual water-cooler

1 or multiple water cooled Opticlimates can be connected to 1 water cooler. The water cooler is a 

super efficient way to recirculate water or a glycol-mix in a closed loop system. The fan(s) and the 

circulation-pump are the only parts that consume energy. The water cooler makes it possible to 

prepare water for the Opticlimates at outside temperatures over 40°C.*

Setting up the system starts with a good design of the system. Pump-size,  piping diameter and 

layout are the most important items when designing the system. 

The pump:

The circulator pump must supply a pre defined flow at a given pressure. The flow is determined by 

the energy that must be circulated (KW) and the pressure depends on the pressure-drop of the 

complete system (Opticlimate(s) +  water-cooler) We always calculate the correct pump for

your setup. We suggest to place the pump indoor.

The piping:

We suggest to use PE-piping with quick connectors. Prevent knees or other fittings that reduce 

water-flow. We supply all the fittings for PE piping in the package. Supplying the piping is also 

possible.

The water cooler:

The stock water coolers come as Industrial heavy duty and Ultra light /compact. The stock versions 

are all vertical models (roof/floor or wall mount). Both models can also be ordered as a horizontal 

model (roof /floor mount)

The fittings:

Supplied fittings are for PE piping applications. We supply automatic bleeders, air separators, ball 

valves, treated fittings depending on your setup. 

© TCF 2019

© TCF 2019

Summary of Contents for 3500pro3

Page 1: ...y the energy that must be circulated KW and the pressure depends on the pressure drop of the complete system Opticlimate s piping water cooler We always calculate the correct pump for your setup We suggest to place the pump indoor The piping We suggest to use PE piping with quick connectors Prevent knees or other fittings that reduce water flow We supply all the fittings for PE piping in the packa...

Page 2: ...te on 1 water cooler The system is filled with water or glycol mix The water supply 8 must be located at the lowest point of the system Automatic bleeders 2 must be located at the highest point of the system A manometer 4 is positioned on the both the return and supply side of the pump The air separator 5 must be located at a location where the pressure in a running system is the lowest pump intak...

Page 3: ...be well designed It s best to consult us using a drawing or sketch of the situation on the Design sheet below Setting up manual Fan pump control Tekening The most simple and cheap way of fan and pump control is to power the pump always and connecting the fan of the water cooler to connection N and 7 inside the electric compartment of the Opticlimate The flow in this setup must be manualy adjusted ...

Page 4: ...mer On off model Opticlimate Inverter model Opticlimate When using an on off model Opticlimate find the cable that powers the compressor coming from relays KM1 Cable code U V or W When using an inverter model Opticlimate find the cable that powers the inverter PCB or compressor The current clamp can be opened to clamp around the cable Plug the other end into the controller The cable is labeled CO2...

Page 5: ...plied communication cable to connect the controllers AUX connection on top with the fan aux box AUX IN connection on the left side The power outlet marked FAN on the fan aux box must be connected to the fan of the water cooler and the pump must be connected to the outlet marked RH The settings on the controller are pre set Do not change them without consultation Power both the controller and fan a...

Page 6: ...rature supply to water cooler C03 Water in temperature return from water cooler Example C02 45 C C03 39 C ΔT 6 K Balancing with manual or auto by pass Adding glycol to the system In an environment where glycol antifreeze in case of a leak could come in contact with food chemicals or in a pharmaceutical or agriculture plant propylene glycol must be used We recommend to use a 20 glycol water mix ant...

Page 7: ... the calculated amount of glycol then top up the system with water until the static pressure is 1 5bar When adding glycol to system that is already pressurised and full with water remove more water than the amount of glycol you want to add add the calculated amount of glycol and top up with water until the static pressure of the system is 1 5bar Note Pure water cools better than a glycol water mix...

Page 8: ...__pro3 pro4 Distance between Opticlimates and water cooler_________________________________mtr Heat load Opticlimates KW _________________________________________________KW Max outside temperature ____________________________________________________ C Min outside temperature ____________________________________________________ C Sketch of the situation TCF 2019 ...