TXP Inst. & Maint. Manual: IM-825
33
adjust the maintenance intervals for
cleaning accordingly.
•
Use as a fan in wet, steamy envi-
ronments is not permitted.
•
Depending on the application, addi-
tional standards or regulations may
have to be observed.
5.3 Permissible installation po-
sitions
The fan may only be placed standing,
with the console facing down. Other po-
sitions and installation positions are not
permitted.
Fig. 20: List
5.4 Assembly
Preconditions:
•
Voltage must match the information
on the nameplate on the frequency
inverter
•
Compliance with local safety regu-
lations, particularly AMCA 410
•
Wearing protective equipment (pro-
tective gloves, work clothes, safety
shoes, safety helmet)
•
Fan is unpacked and set up
To mount the fan, proceed as fol-
lows:
1. Check the clearance around the
drive motor's ventilation system.
The minimum distances must be
maintained.
Power
Minimum dis-
tance to the fan
hood
≤
2 HP (1,5 kW) 1.34 in. (34 mm)
> 2 HP (1,5 kW) 2.09 in. (53 mm)
Table 6: Clearances to fan hood
2. Check the clearance to walls or sur-
rounding systems on the suction
side (suction nozzle) of the fan.
Ensure an optimal suction ef-
fect of the medium on the suc-
tion side for sufficient space to
walls or overturned systems.
As a rule of thumb, we recom-
mend a minimum distance of
0.5 x suction diameter.
Calculation example: Diameter
intake nozzles 6.49 in. (165
mm) x 0.5 = 3.25 in. (82.5 mm)
Minimum distance to other ob-
jects
3. Attach the fan to the base via the 4
mounting holes on the console.