background image

26 

6.6.3.   Heat tube recuperator 

Maintenance  on  this  type  of  recuperator  is  confined  to 
CLEANING  since  it  does  not  have  any  moving  parts. 
Proceed as follows: 
-  every  month  check  drain  operation  drain  and  remove 
any deposits V 
-  clean  the  finned  block  using  either  warm  water  with 
liposoluble  detergents  if  necessary,  or  a  compressed  air 
jet in the opposite direction to the airflow during normal 
Unit operation. 

6.7. 

ACCESSORIES 

6.7.1.   Control air locks 

TCF "SAL" control air locks do not  require any particular 
maintenance. 
However, we recommend you check the alignment of the 
gears  and  the  movement  of  the  fins,  which  must  not  in 
any circumstance be deflected by the weight of the ducts. 

6.7.2.   External air intake grilles 

These must be cleaned frequently to remove any deposits 
obstructing  the  air  passage  which  would  comprise  the 
efficiency of the entire system. 

6.7.3.   Drip separator 

Every  month  check  that  there  are  no  deposits  of  dust  or 
scale  that  would  impair  separation  efficiency  Clean  the 
separator as follows: 
-  extract  the  drip  separator  from  the  Air  Treatment  Unit, 
removing the panel and the screws 
- completely dismantle the drip separator and clean each 
single fin 
-  restore  normal  operating  conditions,  taking  care  not  to 
bend the fins during separator removal and reassembly. 

6.7.4.   Silencer 

The  silencers  installed  on  TCF  machines  are  of  the 
SOUNDPROOFED PANEL type. 
They do not require any particular maintenance. Any dust 
that  forms  on  them  should  be  removed  with  an  ordinary 
vacuum cleaner. 

6.8. 

TROUBLESHOOTING 

The  most  common  MALFUNCTIONS  in  Air  Treatment 
Units are: 
- reduced flow rate 
- increased flow rate 
- reduction in heat exchanger efficiency 
- reduction in heat recuperator efficiency 
- reduction in humidifier efficiency 
- abnormal noise 

6.8.1 .   Reduced flow rate 

This is the result of an uncontrolled increase in resistance 
in  the  air  moving  circuit  which  alters  the  fan's  operating 
point. The most frequent causes are: 
- excessively clogged filters 
-  formation  of  frost  or  ice  on  the  front  surface  of  the 
prefilters in particularly damp and cold climates on Units 
operating entirely with external air  
-  blockage  of  the  intake  grille(s)  (especially  external  air 
intake) 
- fully or partially closed control air locks 
- activation of the dampers  
- deposits on cell blocks and heat exchangers 
- inefficient fan motor unit drive. 

6.8.2. Increased flow rate 

If  the  sum  of  the  resistances  in  the  air-moving  circuit  is 
less  than  the  value  considered  at  the  design  stage,  the 
most common causes are: 
- incorrect setting of any mechanical flow controls or zone 
air locks 
-  non-replacement  of  filters  after  ordinary  maintenance 
operations 
- open or partially closed inspection doors. 

6.8.3.   Reduction in heat exchanger efficiency 

The most common causes are: 
- clogging of finned block 
- formation of air bubbles inside the exchanger 
-  feed  fluids  at  temperatures  lower  than  the  design 
temperature 
- malfunction or breakdown of control valve actuators  
- water flow rate below design values. 

For steam-operated exchangers: 
- malfunctioning of condensate drains 
- reduced supply steam pressure. 

For cooling gas-operated exchangers: 
- malfunctioning of expansion valve 
-  reduced  cooling  capacity  due  to  working  temperatures 
different from those envisaged. 

6.8.4.   Reduction in heat recuperator efficiency 

For crossover flow recuperators the causes may be: 
- dust and dirt on the heat exchanger block 
- clogging due to the presence of foreign  matter  between 
the heat exchanger fins 
- abnormal bypass of air on recuperator 

For two-phase gas recuperators the causes may be: 
- dust and dirt on the heat exchanger block 
- clogging due to the presence of foreign  matter  between 
the heat exchanger fins 
- abnormal bypass of air on recuperator 
- loss of cooling capacity due to accidental failure 

Summary of Contents for ZAE Series

Page 1: ...1 INSTALLATION OPERATION AND MAINTENANCE MANUAL AIR HANDLING UNITS ZAE SERIES ...

Page 2: ...ging duct section between Unit delivery inlet and obstruction 18 5 3 2 Elbows 19 5 3 3 Control air locks 19 6 MAINTENANCE 20 6 1 FOREWORD 20 6 2 FILTRATION SECTIONS 20 6 2 1 Reconditionable synthetic filters 20 6 2 2 Metal filters 20 6 2 3 Rotary filters 21 6 2 4 Reconditionable bag filters 21 6 2 5 Non reconditionable medium high efficiency filtration sections 21 6 2 5 1 Non reconditionable bag f...

Page 3: ... ryto commissioning The recommendations that follow are intended to ensure continuous operation of the Air Treatment Unit and long machine life The procedures described below should be followed by skilled personnel with a good working knowledge of air conditioning systems engineering and air treatment units even though the unit can be operated by those unfamiliar with air treatment thanks to the m...

Page 4: ...g product compliance with prevailing European Union machine directives 2 2 PACKING The Air Treatment Units are usually supplied as fully assembled monoblocks Only if the customer expressly requests it can the units be broken down into several sections to facilitate transportation and carriage through narrow apertures stairs or corridors Transportation of the machines both monoblock and broken down...

Page 5: ...steps must be taken first Prior to installation position the Unit and the accessories in a place affording the best possible protection against accidental knocks dust and atmospheric agents Carefully cover the inlets and outlets to prevent foreign matter from entering the unit and damaging the internal components Extract the pre filters from the Unit and put them in a protected place to preserve t...

Page 6: ...nctioning of the condensate drains difficulty in opening and closing the inspection doors The horizontal alignment of the support surface must be checked with a SPIRIT LEVEL adjustments may be made using STEEL SHIMS 3 3 3 Vibration damping In order to ensure effective protection against vibrations the Air Treatment Unit must be installed as follows suitable DAMPERS in material designed to withstan...

Page 7: ... assembled parts are perfectly aligned and level fig 8 Fasten the sections together with screws in the holes provided The holes are located on the inside of the corners and in the case of dimensions greater than 1 3 m also in a midway position The screw fastening areas can usually be accessed from the inspection doors Otherwise you must remove the panels next to the area involved Should the Unit b...

Page 8: ...pport the connecting pipes The weight of the pipes must under no circumstances bear down on the manifold 4 2 1 Water exchange In order to ensure an optimum heat exchange you must WASH the heat exchanger before connecting it to the water mains once installed in a workmanlike fashion any air present in the hydraulic circuit must be expelled using the relevant valve To allow easy extraction of the ex...

Page 9: ...ons to prevent the likelihood of rupture at the joint between manifolds and copper pipes In order to ensure correct operation of the thermal expansion valve the bulb of the valve must be in perfect contact with the intake line and fitted on the outside of the air flow so as not to be affected by it Special care must be taken with the SIPHONING of these exchangers to ensure the maximum heat exchang...

Page 10: ...be taken to ensure that the base is level see section 3 3 2 The steam system must be complete with all the necessary regulating filtration and safety devices which must be correctly sized Each heat exchanger must be fitted with a condensate drain which must be oversized to allow drainage of the greater quantity of condensate that is formed during system start up Provision must also be made for the...

Page 11: ...arise in which there is no water in the tank the pump motor would overheat and be irreparably damaged Conversely if there is too much water in the tank an overflow may result leading to flooding of the unit and the installation room 4 3 5 Ultrasonic steam submerged electrodes compressed air humidification For Air Treatment Units with the above listed types of humidification you should consult the ...

Page 12: ...tion of the prefilters located in the relevant counter frames with safety springs or guides The electrical connection and installation instructions for the rotary filtration section are provided in the specific manual provided The instructions for introduction of the reconditionable filtration diaphragm are set out in the maintenance chapter 6 2 3 After removing the filters from the packing in whi...

Page 13: ... motor start up system is obtained by connecting the motor direct to the power supply However this method has limitations due to the high start up current pick UD this type of start up is recommended for power ratings of up to 5 5 KW at which TCF installs 4 pole 220 380 V three phase motors as standard The wiring diagrams are shown in fig 27 4 6 1 2 Connecting with delta star starter If the motor ...

Page 14: ...f the same size but with separate windings 4 6 1 4 Permitted start time With regard to the temperature increase the start up time of a motor may not exceed the value shown in table 1 In the case of repeated starts with unchanging rated power the temperature of the motor must be the same as it was before the first start Therefore in order for the values in the table to be valid it is assumed that t...

Page 15: ...cularly important both during the design and installation phases The sound pressure values of our machines are indicated In our technical catalogues or can be supplied directly by our Technical Department according to the requested air moving characteristics Being therefore aware of the sound emissions produced by the Unit the Designer must make sure that in treated environments maximum values lai...

Page 16: ... check that the motor protection devices are sized for the maximum amperage corresponding to the rated value lf the protection devices are sized for an amperage in excess of the rated value you must make sure that the working range is sufficient 5 2 2 Flowrate check Using an oil or water column pressure gauge or an analogue and or digital gauge check the FLOW RESISTANCE in the various filtration s...

Page 17: ...er operating conditions should be made on the remote control power switches inside the control board using an amperometer clamp Under no circumstances must the measurements be made directly on the motor terminals since this is possible only with the inspection door open a condition that would alter the length of the air circuit and therefore the working point of the fans Descend vertically from th...

Page 18: ...M based on the charts developed by AMCA AIR MOVING AND CONDITIONING ASSOCIATION To calculate the additional flow resistance a graph is used which presents a family of straight lines on logarithmic velocity flow resistance coordinates Each line which is identified by a different letter of the alphabet represents an abnormal situation that determines an additional flow resistance AMCA lists the adve...

Page 19: ...FLOW RESISTANCE VALUES according to the Se sp ratio should the locks be installed on the delivery inlet If the air locks are supplied by TCE consult the SAL air lock technical bulletin Abnormal situations in relation to the reference standard may also occur on the intake and are basically connected with the possible formation of eddies caused by curves in the inlet conduit in conflict with the fan...

Page 20: ...the filtration diaphragm is washed without removing it from the frame if necessary using domestic detergents To avoid damaging the filter the temperature of the water must not exceed 50 C Do not use solvents or caustic soda Let the diaphragm dry by evaporation and refit it only when it is perfectly dry TCF advises you to CHECK THE CONDITION OF THE FILTERS ON A WEEKLY BASIS THE PREFILTERS MUST BE R...

Page 21: ...he aperture uppermost rinse them with a weak jet of warm water 50 C max letting the impurities run out at the bottom through the filtration diaphragm let the filters dry thoroughly by evaporation before refitting them Do not use air jets to dry them In this way the filters can be cleaned 2 3 times after which the filter s characteristics will be compromised and it will have to be replaced 6 2 5 No...

Page 22: ...freezing with the arrival of winter For this purpose TCF recommends the following steps In the case of prolonged idleness of the heat exchanger circuits they should be completed drained Where an anti freeze system based on heating elements is provided to protect the exchanger make sure that the control board is constantly powered up On systems operating with anti freeze check its efficiency and to...

Page 23: ...ows stop the electrical pump cut off the water feed using the relevant gate let the block dry completely keeping the fan in operation remove the frame housing the block by undoing the securing screws and lift it out of the unit through the inspection door extract the fouled block from the housing and replace it with another of the same size Take care with the direction of fluid flow the water whic...

Page 24: ...ed with grease nipples require periodic lubrication The greasing intervals under normal operating conditions are shown in Table 11 TABLE 10 Greasing of motor bearing NOTE The bearings must be greased more frequently in harsh operating conditions 6 5 3 Drive In order to ensure optimum drive efficiency and to avoid damaging the fan motor unit the drive must be kept in perfect working order The follo...

Page 25: ... case of drives with several belts the belts must be replaced at the same time This means that there must not be belts presenting different states of wear in the same drive system the number of belts must always match the number of races in this type of drive system the belt slack must be on the same side as shown in Hg 40 before they are tensioned 6 6 Heat recuperator 6 6 1 Crossover flow static ...

Page 26: ... rate This is the result of an uncontrolled increase in resistance in the air moving circuit which alters the fan s operating point The most frequent causes are excessively clogged filters formation of frost or ice on the front surface of the prefilters in particularly damp and cold climates on Units operating entirely with external air blockage of the intake grille s especially external air intak...

Page 27: ...s working life 7 SAFETY 7 1 SAFETY RELATED FEATURES OF AIR TREATMENT UNIT TCF Srl has fitted its Air Treatment Units with every possible safety feature to prevent accidents especially during start up and maintenance Some of these SAFETY FEATURES are listed below INSPECTION DOORS THAT CAN ONLY BE OPENED WITH A KEY are installed in the sections housing rotating parts and drives the GRATES and HOUSIN...

Page 28: ...ano di Granarolo E BO Declares that the following products AIR HANDLING UNIT Mod ZAE Customer Reference Order n Construction year is in compliance with the following Directives 2004 108 CE 2006 42 CE 91 368 CEE 93 68 CEE 2006 95 CE IT IS NECESSARY HOWEVER TO VERIFY THAT THE INSTALLATION AND THE DRIVE ARE CARRY OUT TO YOU CORRECTLY AND IN THE RESPECT OF DIRECTIVES EMC 2004 108 CE AND 2006 42 CE and...

Page 29: ...hould be sent prepaid to our headquarters and the replacement will be sent carriage forward Please note too that the warranty does not include the services of our personnel for the replacement of the part on site this cost is entirely for the installer s account On receipt of the returned material deemed to be defective an inspection will be carried out to establish whether the part reveals abnorm...

Page 30: ...30 ...

Reviews: