HGL Manual
5.0 PQconnect Connectivity
29
Write Parameters:
Table 16: Network Interface INPUT/Setpoint Register Map
Parameter Name
I/O Reg
Address
Offset
Direction
Data Values and
Examples
Description
STATUS_FILTER_A_RELAY_ACTION
540
Input
0 = Disabled
DEFAULT: 9
Range 0 to 65535
To Enable desired status detections, enter
bit mask from table by converting to
decimal.
If a status is active and the bit
corresponding to that status in this mask is
set, the relay will be activated.
Reference Table 18 below for filter status
detection bits. *
STATUS_FILTER_B_RELAY_ACTION
541
Input
0 = Disabled
DEFAULT: 49151
Range: 0 to 65535
STATUS_LINE_RELAY_ACTION
542
Input
0 = Disabled
DEFAULT: 71
Range: 0 to 65535
To Enable desired status detections, enter
bit mask from table by converting to
decimal.
If a status is active and the bit
corresponding to that status in this mask is
set, the relay will be activated
Reference Table 19 below for line status
detection bits. *
STATUS_FILTER_LOAD_RELAY_ACTION
543
Input
0 = Disabled
DEFAULT: 63
Range: 0 to 65535
To Enable desired status detections, enter
bit mask from table by converting to
decimal.
If a status is active and the bit
corresponding to that status in this mask is
set, the relay will be activated.
Reference Table 20 below for load status
detection bits. *
CNT_CLOSE_LOAD_THERSHOLD
570
Input
DEFAULT:
30 =
30%
Range: 10 to 100 %
Contactor close threshold in percent rated
current*
CNT_CLOSE_LOAD_HYSTERESIS
571
Input
DEFAULT:
5 = 5%
Range: 2 to 50 %
Contactor will open when it reaches the
hysteresis *
CNT_CLOSE_KVAR_THERSHOLD
572
Input
DEFAULT:
50 = 50
kVAR
Range: 0 to 1000
kVAR
Contactor close threshold for kVAR
control*
CNT_CLOSE_KVAR_HYSTERESIS
573
Input
DEFAULT:
10 =
10%
Range: 5 to 100 %
Contactor will open when it reaches the
hysteresis *
CNT_CLOSE_DELAY
574
Input
DEFAULT:
5 = 5
seconds
Range: 1 to 3600
seconds
Contactor Close Delay*
CNT_OPEN_DELAY
575
Input
DEFAULT:
5 = 5
seconds
Range: 1 to 3600
seconds
Contactor Open Delay*