HGL Manual
5.0 PQconnect Connectivity
34
Read Parameters:
Table 23: Network Interface OUTPUT/Feedback Register Map
Parameter Name
I/O Reg
Address Offset
Direction
Data Values and
Examples
Description
P_LOAD_APPARENT_TOTAL 120
Output
100 = 100 kVA
Range: 0 to 1000 kVA Total Filter output apparent power
P_LOAD_REAL_TOTAL
121
Output
100 = 100kW
Range: 0 to 1000 kW
Total Filter output real power
P_LOAD_REACTIVE_TOTAL 122
Output
100 = 100 kVAR
Range: 0 to 1000 kVAR
Total Filter output reactive power; Negative number
indicates inductive power. Positive number indicates
capacitive power
P_LOAD_POWER_FACTOR
123
Output
1,000 = 1.00 Unity PF
-95 = 0.95 Lagging PF
95 = 0.95 Leading PF
Range: -99 to 1000
Filter output Displacement Power Factor - Negative
values indicate lagging power factor
I_LINE_A_HARM_1
140
Output
Fundamental = 1000 =
100%
Range: 0 to 100 %
Filter input phase A spectrum data. Data points from
the fundamental to the 25
th
harmonic. If the user
would like the full spectrum data points up to the 50
th
harmonic; the user will have to run the full data
capture command.
I_LINE_A_HARM_3
141
Output
I_LINE_A_HARM_5
142
Output
I_LINE_A_HARM_7
143
Output
I_LINE_A_HARM_11
144
Output
I_LINE_A_HARM_13
145
Output
I_LINE_A_HARM_17
146
Output
I_LINE_A_HARM_19
147
Output
I_LINE_A_HARM_23
148
Output
I_LINE_A_HARM_25
149
Output
I_LINE_B_HARM_1
160
Output
Fundamental = 1000 =
100%
Range: 0 to 100 %
Filter input phase B spectrum data. Data points from
the fundamental to the 25
th
harmonic. If the user
would like the full spectrum data points up to the 50
th
harmonic; the user will have to run the full data
capture command.
I_LINE_B_HARM_3
161
Output
I_LINE_B_HARM_5
162
Output
I_LINE_B_HARM_7
163
Output
I_LINE_B_HARM_11
164
Output
I_LINE_B_HARM_13
165
Output
I_LINE_B_HARM_17
166
Output
I_LINE_B_HARM_19
167
Output
I_LINE_B_HARM_23
168
Output
I_LINE_B_HARM_25
169
Output
I_LINE_C_HARM_1
180
Output
Fundamental = 1000 =
100%
Range: 0 to 100 %
Filter input phase C spectrum data. Data points from
the fundamental to the 25
th
harmonic. If the user
would like the full spectrum data points up to the 50
th
harmonic; the user will have to run the full data
capture command.
I_LINE_C_HARM_3
181
Output
I_LINE_C_HARM_5
182
Output
I_LINE_C_HARM_7
183
Output
I_LINE_C_HARM_11
184
Output
I_LINE_C_HARM_13
185
Output
I_LINE_C_HARM_17
186
Output
I_LINE_C_HARM_19
187
Output
I_LINE_C_HARM_23
188
Output
I_LINE_C_HARM_25
189
Output