Section 7.0 HMI Introduction
HGA IOM
79
Status Screen
The Status screen shows more specific information on the performance of the system, such as
current and Voltage waveforms, Power Factor and information specific to the Line/Load screen
and Converter screen.
Note:
The Status Screen will indicate if unit is Line Side/Load Side. The “Line/Load” button and
the “Line/Load Current Plot” text changes to show Line or Load status.
The figure below explains the main “Status” screen.
Line Side
Load Side
Note:
The Status Screen will indicate if unit is Line Side/Load Side. The “Line/Load” button and
the “Line/Load Current Plot” text changes to show Line or Load status.
Figure 36: Status Screen
Table 23: Status Screen Elements
Screen Element
Description
Line/Load Button
Use this button to get to the “Line/Load Status” Sub Screen
Volts Display
Displays the current utility phase to phase line Voltage in Volts
RMS.
Current Display
Displays the current line/load phase current in Amps RMS.
Power Factor Display
Displays current line/load power factor. A value of 1.00
indicates unity power factor. A negative power factor indicates
lagging power factor.
Frequency Display
Displays the current utility line frequency in Hz.
Run/Stop Button
Runs and stops the HarmonicGuard
®
Active filter.
Converter Button
This button will take the user to the “Converter Status” Sub
Screen.