20

 

 

 

 

Figure 8: Waveform After MotorShield

 

 

This waveform illustrates typical filter output voltage waveforms when measured from line to line. 

If the measured waveform does not resemble a sine wave like this illustration, and looks more like 

the filter input waveform, troubleshoot filter wiring and components. 

 

 

Warning 

Only qualified electricians should carry out all electrical installation and maintenance 

work on the MotorShield™. 
Exercise caution when checking waveforms with an oscilloscope. 
Use a dual probe, differential input set-up, or other means of isolating the scope 

chassis from the motor voltage. 
Disconnect power when attaching and removing the probes. 

 

Replacement Parts 

If replacement parts are needed, please contact your TCI representative. To ensure that the 

MotorShield

 

continues to perform to its original specifications, replacement parts should conform 

to TCI specifications. 

Factory Contacts and Tech Support 

You can contact TCI directly at 800-824-8282. Select "Customer Service" or "Technical Support" 

and have your MotorShield

 

nameplate information available. 

Typical Outline Drawings 

Typical MotorShield

 

drawings are provided on the TCI website. These drawings provide general 

information describing your MotorShield

 

filter. All dimensions on the drawings are in inches.  More 

specific information is provided by the drawings shipped with the unit. Be sure to carefully review the 

information provided by these drawings. The information on these drawings takes precedence over the 

information provided in this manual. You can find the drawings at 

https://transcoil.com/products/motorshield-sinewave-filter/msd-ratings-tables/ 

 

 

 

Summary of Contents for MotorShield MSD0009A300

Page 1: ...allation Operation and Maintenance Manual TCI LLC W132 N10611 Grant Drive Germantown WI 53022 Phone 414 357 4480 Fax 414 357 4484 Helpline 800 TCI 8282 www transcoil com 2019 TCI LLC All right reserved Product No 29343 Effective 10 15 19 Version F ...

Page 2: ......

Page 3: ...ion 12 Variable Frequency Drive Settings 12 Environment 12 Working Space 12 Power Wiring 12 Thermal Switch 13 Optional Features 13 4 0 Installation Guidelines 14 Wiring 14 Before Connecting 14 Over Temperature Switch 14 Field Wiring Connection Terminals 14 Connection Diagram 16 Grounding 16 Power Wiring 16 5 0 Operation 17 Variable Frequency Drive Settings 17 Start Up Commissioning 17 Before Apply...

Page 4: ...drawings in Section 6 6 16 17 E Updates to Product Ratings and Dimensions Table Updates to Installation Checklist 9 18 17 F Revision of technical specifications and overall reformat 1015 19 We strive to provide the most up to date and accurate documentation available at the time of printing Please visit www transcoil com for the most recent revision of this manual ...

Page 5: ...tion readers about conditions which can if proper steps are not taken lead to a serious fault condition physical injury or death Cautions are used to draw attention to instructions Failure to properly follow such instructions may lead to a malfunction and possible equipment damage Warnings Readers are informed of situations that can result in serious physical injury and or serious damage to equipm...

Page 6: ... Verify with a voltmeter to make sure that all sources of power have been disconnected and that all capacitors have discharged before beginning work Caution The drive output terminals MotorShield and the motor cables are at a dangerously high voltage when power is applied to the drive regardless of motor operation Warning All wiring must be in accordance with the National Electrical Code NEC and o...

Page 7: ... checklist for a successful installation These points are explained in detail in the subsequent sections of this manual Receiving Inspection The MotorShield has been thoroughly inspected functionally tested at the factory and carefully packaged for shipment When you receive the unit you should immediately inspect the shipping Make sure that the installation location is appropriate for the enclosur...

Page 8: ... is expressly limited at TCI s option to i repair or replacement of that product or ii return of the product and refund of the purchase price Such remedy shall be Buyer s sole and exclusive remedy TCI SHALL NOT IN ANY EVENT BE LIABLE FOR INCIDENTAL DAMAGES OR FOR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LOSS OF INCOME LOSS OF TIME LOST SALES INJURY TO PERSONAL PROPERTY LIABILITY BUYER IN...

Page 9: ... the output voltage waveform resulting in a nearly pure sine wave voltage profile The MotorShield sine wave filter reduces the effects of the reflected wave phenomenon dV dt which can cause motor heating insulation damage and excessive audible noise The reduction of high frequency VFD output currents extends the life of motors and transformers and eliminates the need for special motor cables The M...

Page 10: ...on Typical Configuration for MSD 480 V 9A to 16A Typical Configuration for MSD 480 V 23A to 45A Figure 1 Typical Configurations for the MotorShield Filter These drawings are for general reference only Use the drawings supplied with the unit for installation ...

Page 11: ...al Configuration for MSD 480 V 55A Typical Configuration for MSD 480 V 65A and up Figure 2 Typical Configurations for the MotorShield Filter These drawings are for general reference only Use the drawings supplied with the unit for installation ...

Page 12: ...age FLA the rated continuous operating current RMS amps System Voltage the maximum VFD output voltage fundamental Hz the maximum VFD output frequency fundamental Phase 3 The MotorShield is designed for use only with 3 phase loads Drawing and Schematic outline and mounting dimension of filter with schematic diagram Manufacturing for TCI internal use Enclosure Type UL Type 1 3R Figure 3 Example of M...

Page 13: ...ated 110 Amps 480 V Figure 4 MotorShield Model Number Encoding The MotorShield has a current rating rather than a horsepower rating The rating and dimension tables in the following section list the nominal horsepower ratings corresponding to the current ratings of the standard models Standard Product Ratings and Dimension Tables The following table lists the ratings and dimensions of the standard ...

Page 14: ... 72 cm 645 MSD0130A300 100 130 187 lbs 85 Kg 22 13 in 56 cm 20 43 in 52 cm 28 50 in 72 cm 827 MSD0160A300 125 160 340 lbs 154 Kg 36 00 in 91 cm 28 40 in 72 cm 36 86 in 94 cm 683 MSD0200A300 150 200 425 lbs 193 Kg 36 00 in 91 cm 28 40 in 72 cm 36 86 in 94 cm 1025 MSD0250A300 200 250 450 lbs 204 Kg 36 00 in 91 cm 28 40 in 72 cm 36 86 in 94 cm 1153 MSD0305A300 250 305 460 lbs 209 Kg 36 00 in 91 cm 28...

Page 15: ...ance Maximum peak voltage of output waveform 480 V models 1000 V 600 V models 1 500 V Maximum dV dt of output waveform 480 V models 500 V μs 600 V models 1 500 V μs Environmental Conditions Maximum Elevation 6 600 feet 2 000 m derating required for operation above this level Ambient Operating Temperature Range 30 C 22 F to 40 C 104 F Cooling provisions required for operation above this temperature...

Page 16: ...roved for such use this equipment is not suitable for use in an explosive atmosphere or in a Hazardous Classified Location as defined in article 500 of the National Electrical Code NEC Make sure that the installation location will not be exposed to corrosive or combustible airborne contaminants excessive dirt of liquids The unit must be installed in an environment where it will not be exposed to C...

Page 17: ...itors overheat Connect these switches to monitoring equipment Figure 5 Thermal Switches Optional Features Additional wiring requirements may apply to MotorShield units that are equipped with optional features For instructions covering these additional requirements refer to drawings and or other supplemental information furnished with the unit Reactor Thermal Switch Capacitor Thermal Switch ...

Page 18: ...r Failure to follow the safety instructions set forth in this manual can result in serious injury or death Warning Exercise caution when connecting the filter to the drive Internal filter components may carry dangerous voltage which can cause death or serious injury upon contact Over Temperature Switch A set of over temperature switches is supplied to prevent damage to the filter in the rare case ...

Page 19: ... 35 lb in 4 0 N m B 30 10 AWG 30 lb in 3 4 N m A 30 10 AWG 40 lb in 4 5 N m B 35 8 AWG 30 lb in 3 4 N m A 35 8 AWG 40 lb in 4 5 N m B 45 8 AWG 30 lb in 3 4 N m A 45 8 AWG 45 lb in 5 1 N m B 55 6 AWG 35 lb in 4 0 N m A 55 6 AWG 45 lb in 5 1 N m C 65 6 AWG 45 lb in 5 1 N m C 65 6 AWG 45 lb in 5 1 N m C 80 4 AWG 50 lb in 5 7 N m C 80 4 AWG 50 lb in 5 7 N m C 110 2 AWG 50 lb in 5 7 N m C 110 2 AWG 50 ...

Page 20: ... the requirements of the National Electrical Code NEC and or any other codes that apply to the installation site The ground connection must be made using a wire conductor Metallic conduit is not a suitable grounding conductor The integrity of all ground connections should be periodically checked Power Wiring Connect the output of the VFD terminals T1 U T2 V T3 W to the input of the MotorShield ter...

Page 21: ...configuration Caution Ensure drive output frequency is set between 2 kHz and 16 kHz Failure to do so may result in damage to the filter Caution Thoroughly check the installation before applying power and operating the equipment for the first time Caution The MotorShield can be operated without a load connected to its output terminals for example to facilitate confirmation of system wiring however ...

Page 22: ...ricians should carry out all electrical installation and maintenance work on the MotorShield Disconnect all sources of power to the VFD and MotorShield before working on the equipment Do not attempt any work on a powered MotorShield Check to see that the installation environment remains free from exposure to excessive dirt and contaminants Refer to the Pre installation Planning section of this man...

Page 23: ...xceeds its ratings a switching frequency lower than its minimum specification a motor frequency that exceeds maximum specifications or blocked air flow Check to make sure current drive switching frequency and drive output fundamental frequency meet product specifications Check to make sure ventilation openings are open and not blocked or clogged Ensure reactor is not covered with a thick layer of ...

Page 24: ...rts are needed please contact your TCI representative To ensure that the MotorShield continues to perform to its original specifications replacement parts should conform to TCI specifications Factory Contacts and Tech Support You can contact TCI directly at 800 824 8282 Select Customer Service or Technical Support and have your MotorShield nameplate information available Typical Outline Drawings T...

Page 25: ...I LLC W132 N10611 Grant Drive Germantown WI 53022 Phone 414 357 4480 Fax 414 357 4484 Helpline 800 TCI 8282 www transcoil com 2019 TCI LLC All right reserved Product No 29343 Effective 10 15 19 Version F ...

Reviews: