background image

V1k 

Installation 

Guide

TCI, LLC

W132 N10611 Grant Drive

Germantown, Wisconsin 53022

Ph: 800-TCI-8282

www.transcoil.com

Revision E 

        Part # 25316 

June 7, 2016

TCI, LLC

W132 N10611 Grant Drive

Germantown, Wisconsin 53022

Ph: 800-TCI-8282

www.transcoil.com

Field Wiring

Field Wiring Connection Terminals

Compression type terminals are provided for all line 
wiring connections. Th

  e wire size capacity ranges and 

tightening torque for the power terminals are listed in the 
table.

Warnings and Cautions

Dangerous Voltage Warning: warns of 
situations in which a high voltage can 
cause injury and/or equipment damage. 
Th

  e text next to this symbol describes 

ways to avoid danger.

General Warning: warns of situations 
that can cause physical injury and/
or equipment damage by means other 
than electrical. Th

  e text next to this 

symbol describes ways to avoid the 
danger.

General Safety Instructions

Be sure to read, understand, and follow 
all safety instructions.

Only qualifi ed electricians should 
carry out all electrical installation and 
maintenance work on V1k drive output 
fi lters.

All wiring must be in accordance with 
the National Electrical Code (NEC) 
and/or any other codes that apply to 
the installation site.

Disconnect all power before working 
on the equipment. Do not attempt any 
work on a powered V1k output fi lter.

Th

  e V1k, VFD, motor, and other 

connected equipment must be properly 
grounded.

Th

  e VFD terminals and connected 

cables are at a dangerously high voltage 
when power is applied to the VFD, 
regardless of motor operation.

Warning

Warning

Warning

Warning

Warning

Warning

Warning

Warning

!

!

!

!

See www.transcoil.com for dimensions tables. Please contact 
TCI Technical Support or your TCI distributor for application 
information regarding the use of V1k output fi lters on the 
output side of the VFD.

V1k Model 

Numbers

Input and Output Motor Power

Wire Size

Torque 

(in.-lb.)

V1k2A to V1k12A

12 - 14

10

V1k16A

4 - 12

20

V1k18A to V1k21A

4 - 10

20

V1k25A to V1k27A

4 - 8

20

V1k35A

6 - 8

30

V1k45A

6

30

V1k55A

1 - 4

35

V1k80A

1 - 3

35

V1k110A

2/0 - 1/0

50

V1k130A

2/0

50

V1k160A

250 MCM - 3/0

375

V1k200A

two 2/0 - 1

50

V1k250A

two 2/0

50

V1k305A

two 350 MCM - 3/0

375

V1k362A

two 350 MCM - 4/0

375

V1k420A

two 600 MCM - 300

500

V1k480A

two 600 MCM - 350

500

V1k600A

two 600 MCM - 500 MCM

500

V1k750A

three 600 MCM - 400 MCM

500

All electrical connections must be 
re-torqued annually.

Reviews: