TCNet Boiler Controller
User and Service Manual
11
-8 … -5:C
-/+ 10:C
-4 … -1:C
-/+ 10:C
0 … 3:C
-/+ 10:C
4 … 7:C
-/+ 10:C
8 … 11:C
-/+ 10:C
12 … 15:C
-/+ 10:C
16 … 19:C
-/+ 10:C
>20 :C
-/+ 10:C
If the compensated temperature setpoint exceeds the temperature limits of the boiler, controller will
increase or decrease the setpoint in between minimum and maximum temperature limits.
Day-Night Compensation
Your boiler is olso able to adjust the temperature setpoint according to different time slices in a day.
To setup the day-night compensation,
first navigate to time slice with
navigation keys and select the
time slice with
adjust keys.
After selecting the time slice,
navigate to Correction value and set
the offset temperature of your boiler
for this time slice. To adjust another
time slice, navigate back to time slice
with
navigation keys and select the time slice that you want. After all settings have been
completed, navigate to <Return and press
Input key to return to the User Preferences Menu.
There are eight time slices to adjust.
00:00 – 02:59
03:00 – 05:59
06:00 – 08:59
09:00 – 11:59
12:00 – 14:59
15:00 – 17:59
18:00 – 20:59
21:00 – 23:59
If the compensated temperature setpoint exceeds the temperature limits of the boiler, controller will
increase or decrease the setpoint in between minimum and maximum temperature limits.