28.

ENABLE MOD OUT 1

26.

MIN POS?              YES

AQUASTAT?           YES

SETPOINT:            065F

25.

ENABLE ANALOG:

                         

AQUASTAT?        YES

23.

MOD OUT 1

TYPE:         ENDPOINT

22.

SET CONTROL

MODE:                    P+I

24a.

program

setup

MOD OUT 1

MIN POS:            10%

27.

program

setup

TIME CLOCK OUTPUT

OCCUPIED=CLOSED

program

setup

MOD OUT 1

IS:                       HEAT

24b.

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

STAGE 2

DIFF:                        1F

21.

STAGE 2

OFFSET:                  1F

20.

19.

STAGE 1

DIFF:                        1F

STAGE 1

OFFSET:                 0F

18.

STAGE OUTPUT 1&2

17.

AS:       HEAT & COOL

SET OVERRIDE

TIME:     180 MINUTES

16.

LIMIT SETPOINT

15.

/-:              5F

14.

UNOCCUPIED COOL

SETPOINT:             80F

13.

OCCUPIED COOL

SETPOINT:             72F

program

setup

Occupied Cool Setpoint  Screen.

 Set 

the occupied cool setpoint.

Unoccupied Cool Setpoint Screen.

 

Set the unoccupied cool setpoint.

User Setpoint Limit Screen.

 Enter the 

number of degrees you want the user to 

be allowed to change the preset occu-

pied setpoints up or down.

Override Time Screen.

 Enter the   

number of minutes (0 to 255) that the 

SZ1018 will maintain occupied setpoints 

when overridden.  

Stage Mode Screen.

 Choose whether 

stages 1 and 2 perform heating or cool-

ing functions, Heat & Cool or whether 

both stages are to be disabled.

Stage 1 Offset  Screen.

 Enter an offset 

value for stage 1. First stage is normally 

0 offset. This screen does not appear if 

stage outputs 1 and 2 are disabled.

Stage 1 Differential Screen.

 Enter a 

differential value for stage 1. This screen 

does not display if stage outputs 1 and 2 

are disabled.

 

 

 

Stage 2 Offset  Screen.

 Enter an offset 

value for stage 2. This screen is not 

displayed if stage outputs 1 and 2 are 

disabled.

 

Stage 2 Differential Screen.

 Enter a 

differential value for stage 2. This screen 

is not displayed if stage outputs 1 and 2 

are disabled.

Control Mode Screen.

 Enter whether you 

want to control by temperature only (P) or 

add a time factor (P+I). This is applies to 

both the stage outputs.

 

Time Clock Output Screen. 

Choose 

whether the auxiliary output will be OPEN 

during occupied periods (and closed during 

unoccupied periods) or CLOSED during 

occupied periods (and open during unoc-

cupied periods).  

Modulating Output 1 Type Screen.

 

Choose whether the modulating output    

will use Endpoint or Midpoint Control.

Modulating Output 1 Define Screen.

 

Choose whether modulating output one is 

used for heat, cool or aquastat.

Analog Aquastat Selection Screen. 

Choose whether to use the discharge air 

sensor (T2) to determine whether analog 

output 1 will be used for heating or cool-

ing. If NO is selected, the next screen is 

skipped. If no is selected, DI 2 will function 

as aquastat where the analog output will be 

used for cooling with DI 2 open and heating 

with DI 2 closed.

Analog Aquastat Input Screen. 

If an 

analog aquastat is selected, choose the set-

point to distinguish when hot or cold water 

is available. If the discharge temperature 

is below this setpoint, analog output 1 will 

do cooling. If the discharge temperature is 

above this setpoint, analog output 1 will do 

heating.

Minimum Position Selection Screen. 

Choose whether to set a minimum posi-

tion constraint for analog output 1. If NO is 

selected, the next screen is skipped.

Zone Damper min. Position Screen.      

Set the minimum position for analog        

output 1.

Modulating Output 1 Action Screen

Choose whether the output will be direct 

or reverse acting. (When DI2 is set to 

AQUASTAT, the output will automatically 

reverse action when DI2 is closed. When 

Analog Aquastat is chosen).
 

Modulating Output 1 Range Screen. 

Choose whether the modulating output 

range will be 0-20 mA or 4-20 mA.

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

5

program

setup

program

setup

program

setup

program

setup

program

setup

33.

MOD OUT 1 SETPOINT

OFFSET:                00F

32.

MOD OUT 1 UNOCC

30.

TYPE:    MODULATING

MOD OUT 1

RANGE:           4-20 MA

29.

MOD OUT 1:

                         

ACTION:       DIRECT

program

setup

MOD OUT 1 PROP.

BAND:                     5F

31.

Summary of Contents for Superzone SZ1018

Page 1: ...t Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Digital or analog changeover Product Manual Contents Descripti...

Page 2: ...devices SZ1018 thermo stats require 8 VA 24 VAC When the SZ1018 are used as a stand alone thermostat without communications the unit transformer may be used to power it However using separate power wi...

Page 3: ...h the two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting sectio...

Page 4: ...s the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is entered it will revert to the previous screen Contro...

Page 5: ...reen Enter whether you want to control by temperature only P or add a time factor P I This is applies to both the stage outputs Time Clock Output Screen Choose whether the auxiliary output will be OPE...

Page 6: ...Choose whether to control based on DISCHARGE air reset or SPACE temper ature This screen will not appear if the discharge air sensor function is disabled Set to SPACE if this stat will be used within...

Page 7: ...n Monitoring Screen Setting Clock Schedule The SZ1018 clock and schedule may be set through the keypad on the face or with a PC For more infor mation on programming through the PC consult your softwar...

Page 8: ...ge air tempera ture will be controlled to this setting by modulating the heating or cooling device Operation UNOCCUPIED SETBACK The SZ1018 operate in either an occupied or unoc cupied mode During the...

Page 9: ...s required which indicates when the fan is running If the thermostat turns on the FAN and DI1 is not closed after thirty seconds the system will go to OFF disabling all outputs the fan LED will turn o...

Page 10: ...parameters for analog output 2 Select whether the analog output is set for heating cooling or aquastat Select direct or reverse action Select whether you want the analog output to modulate from 4 to 2...

Page 11: ...k the wiring Short terminals R to Y W1 or Y W2 and see if the heating or cooling comes on This is a check for a mechanical relay failure Wrong Temperature Display Initially verify the wiring connectio...

Page 12: ...tatus service status 7 MOD OUT 2 100 OPEN service status MOD OUT 2 Screen Shows the percentage of modulating output 2 DI2 and DI3 Status Screen Shows DI2 status and filter status or DI3 status Main Mo...