program
setup
program
setup
program
setup
program
setup
MOD OUT 2 UNOCC
36.
TYPE: MODULATING
MOD OUT 2
RANGE: 4-20mA
35.
MOD OUT 2
ACTION: DIRECT
MOD OUT 2 IS:
HEAT
34.
37.
program
setup
program
setup
41.
DISCHARGE AIR
LOW LIMIT: 45F
40.
ENABLE DISCHARGE
AIR SENSOR? YES
38.
program
setup
MOD OUT 2 PROP.
BAND: 01F
39.
program
setup
MOD OUT 2 SET P
OFFSET: 00F
Modulating Output 1 Unoccupied
Action Screen.
Choose whether the
unoccupied action will be modulating,
0 or 4 mA, or 20 mA.
Modulating Output 1 Proportional
Band Screen.
Enter the number of
degrees away from the setpoint that the
valve or damper will be fully open.
Analog Output 1 Setpoint Offset
Screen.
Enter a setpoint offset. This is a
value below the heating setpoint or above
the cooling setpoint where the analog
output begins to modulate.
Modulating Output 2 Type Screen.
Choose whether the modulating output 2
will be used for heating or cooling.
Modulating Output 2 Action Screen
.
Choose whether the output will be direct
or reverse acting.
Modulating Output 2 Range Screen.
Choose whether the modulating output
range will be 0-20 mA or 4-20 mA.
Modulating Output 2 Unoccupied
Action Screen.
Choose whether the
unoccupied action will be modulating, 0
or 4 mA, or 20 mA.
Modulating Output 2 Proportional
Band Screen.
Enter the number of
degrees away from the setpoint that the
valve or damper will be fully open.
Analog Output 2 Setpoint Offset
Screen.
Enter a setpoint offset. This is a
value below the heating setpoint or above
the cooling setpoint where the analog
output begins to modulate.
Discharge Air Sensor Screen.
Choose
whether or not you are using the discharge
air sensor function. To monitor only, select no.
See setup instructions for dipswitch settings
which must also be set.
Discharge Air Low Limit Screen.
Enter
a discharge air low limit value. This
screen will not appear if the discharge air
sensor function is disabled.
Discharge Air High Limit Screen.
Enter
a discharge air high limit value. This
screen will not appear if the discharge air
sensor function is disabled.
Discharge Air Reset Screen.
Choose whether to control based on
DISCHARGE air reset or SPACE temper-
ature. This screen will not appear if the
discharge air sensor function is disabled.
*Set to SPACE if this stat will be used within
a zoning system.
Discharge Air Enable Heating Low
Limit Screen.
Choose wether to enable
Heating Low temperature Limit.
Discharge Air Setpoint Screen.
Enter a
value at which the discharge air setpoint
is to be controlled. This screen will not
appear if the control is based on space
temperature.
*Do not use with Zoning
System.
Reset Ratio Factor Screen.
Enter a
reset ratio factor. This is the number of
degrees that the discharge air setpoint is
raised when the space temperature falls
by 1 degree for heating, or the number
of degrees that the discharge air setpoint
is lowered when the space temperature
rises by 1 degree for cooling.
*Do not use
with Zoning System.
Outdoor Air Sensor Screen.
Choose
whether or not you are using an outdoor
air sensor function To monitor only, select
no. See setup instructions for dipswitch
settings which must also be set.
Cooling Lockout Screen.
Enter an
outdoor air cooling lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled.
*Do not
use with Zoning System.
Heating Lockout Screen.
Enter an
outdoor air heating lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled.
*Do not
use with Zoning System.
DI1 Choice Screen.
Choose DI1 as FAN
PROVING or a MONITOR point. Select
MONITOR if unused.
R
2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
6
program
setup
program
setup
program
setup
program
setup
program
setup
33.
MOD OUT 1 SETPOINT
OFFSET: 00F
32.
MOD OUT 1 UNOCC
30.
TYPE: MODULATING
MOD OUT 1
RANGE: 4-20 MA
29.
MOD OUT 1:
ACTION: DIRECT
program
setup
MOD OUT 1 PROP.
BAND: 5F
31.
program
setup
program
setup
program
setup
program
setup
MOD OUT 2 UNOCC
36.
TYPE: MODULATING
MOD OUT 2
RANGE: 4-20mA
35.
MOD OUT 2
ACTION: DIRECT
MOD OUT 2 IS:
HEAT
34.
37.
program
setup
program
setup
41.
DISCHARGE AIR
LOW LIMIT: 45F
40.
ENABLE DISCHARGE
AIR SENSOR? YES
38.
program
setup
MOD OUT 2 PROP.
BAND: 01F
39.
program
setup
MOD OUT 2 SET P
OFFSET: 00F
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
50.
DI2 USED FOR:
SERVICE
49.
48.
DI1 USED FOR
FAN PROVING
HEATING LOCKOUT
TEMP: 70F
47.
COOLING LOCKOUT
46.
TEMP: 80F
ENABLE OUTDOOR
AIR SENSOR? YES
45.
RESET RATIO
44.
FACTOR: 2F
DISCHARGE AIR
SETPOINT: 90F
42.
CONTROL BASED
ON: SPACE
DISCHARGE AIR
HIGH LIMIT: 120F
program
setup
program
setup
43b.
ENABLE HEATING
LOW LIMIT? YES
43a.