background image

air temperature rises 2° above the lockout temperature. If
the outdoor temperature rises above the HEATING LOCK-
OUT TEMP, all heating stages will be locked out and will
remain locked out until the outdoor air temperature falls 2°
below the lockout temperature. 
The outdoor air span is -40 to 160 °F (-40.0 to 71.1 °C).

FAN PROVING

The SZ1017N allows DI1 to be set for fan proving to pro-
tect equipment on fan failure. To utilize this, a pressure or
current switch is required, which indicates when the fan is
running. If the thermostat turns on the FAN, and DI1 is not
closed after thirty seconds, the system will go to OFF, dis-
abling all outputs, the fan LED will turn off, and the service
LED will be lit until the system is manually reset by
switching the system to a mode other than OFF.  

DI2 SETPOINT SHIFT

The SZ1017N allows DI2 to be set for setpoint shift for
energy demand setback. This is enabled by setting DI2 to
the MONITOR mode. A digital contact that closes when
setback is needed should be wired into DI2. You may speci-
fy a number of degrees such that, when the thermostat is
operating in the occupied mode, and DI2 is closed, the
heating setpoint will be lowered this number of degrees,
and the cooling setpoint will be raised this number of
degrees. The fan will continue to operate according to its
occupied setting. If you are using DI2 as monitor for anoth-
er purpose, make sure to set the setpoint and shift value to
zero.

STAGE OUTPUT PARAMETERS

The SZ1017N will control up to two stages of either heat-
ing or cooling.
For each stage, you may specify an offset and a differential
value. The offset value is the amount away from the set-
point a stage will turn off. By assigning a stage a value
other than zero, you “anticipate” that the residual heat or
cooling in the duct or the other stages will bring the tem-
perature back to setpoint. In most cases, the first stage is set
to zero. The differential value is the difference between the
on and off points. 

DISCHARGE AIR TEMPERATURE SENSING

The SZ1017N accepts a remote 1000 

discharge air sensor

(TS1009 or TS1002) for monitoring purposes.  (See setup
instructions for dipswitch placement for this option.) 
Choose YES in programming screen #28 only if you are
using a discharge air sensor and you want to enable the dis-
charge air temperature high and low limit functions or dis-
charge air reset function. See Discharge Air Reset section
for further programming options. If NO is chosen, the dis-
charge air is still monitored. 
When the function is enabled, a LOW LIMIT and HIGH
LIMIT are entered in steps #29 and #30. If the HIGH
LIMIT is reached, the fan and heating stages will be turned
off and will remain off until the discharge air temperature
falls 3° below that limit. If the LOW LIMIT is reached, the
fan and cooling stages will be turned off and will remain off
until the discharge air rises 3° above that limit. When either
limit is reached, the service LED will be on until normal
operation resumes.     
The discharge air span is 0 to 150 °F (-17.8 to 65.6 °C).

ANALOG OUTPUT / DISCHARGE AIR RESET

The analog output on the SZ1017N is used to control the
heating or cooling in a space. To use the discharge air reset
function, a discharge air sensor must be installed. In pro-
gramming step #28, the discharge air sensor must be
enabled. In programming step #31, the control must be
based on DISCHARGE air. 
In programming screen #32, you are asked to enter a dis-
charge air setpoint. The discharge air temperature will be
controlled to this setting by modulating the heating or cool-
ing device.

In programming screen #33, you are asked to enter a reset

ratio factor. This  is the number of degrees that the dis-
charge air setpoint is raised when the room temperature falls
below the heating setpoint by 1 degree if the analog output
is set for heating, or the number of degrees that the dis-
charge air setpoint is lowered when the room temperature
rises above the cooling setpoint by 1 degree if the analog
output is set for cooling.

OUTDOOR AIR TEMPERATURE SENSING

The  SZ1017N accepts a remote 1000 

outdoor tempera-

ture sensor (TS1003) for monitoring purposes. (See setup
instructions for dipswitch placement for this option.) 
Choose YES in programming screen #34 only if you are
using an outdoor air sensor and you want to enable the out-
door air heating and cooling lockout functions. If NO is
chosen, the outdoor air is still monitored. 
When the function is enabled, a COOLING LOCKOUT
TEMP and HEATING LOCKOUT TEMP are entered in
steps #35 and #36. If the outdoor temperature falls below
the COOLING LOCKOUT TEMP, all cooling stages will
be locked out and will remain locked out until the outdoor

Heat Setpoint

Cool Setpoint

ON

ON

ON

ON

OFF

OFF

OFF

OFF

Differential

Differential

Offset

Offset

Differential

Differential

R

2800 LAURA LANE 

I

MIDDLETON, WI 53562 

I

(800) 288-9383 

I

FAX (608) 836-9044 

I

www.tcs-basys.com

8

Summary of Contents for SZ1017N

Page 1: ...e locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Product Manual Contents Description 1 Features 1 Mounting 1 N2 Bus Connections 2 Wiring 2 Setup 3 Progr...

Page 2: ...ughout because these are half wave recti fied devices SZ1017N thermostats require 8 VA 24 VAC When the SZ1017N is used as a stand alone thermostat with out communications the unit transformer may be u...

Page 3: ...e two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting section SE...

Page 4: ...S TEMPS SHOWN IN 4 FAHRENHEIT program setup Main Monitoring Screen Press the pro gram setup button to access the following screens Access Code Entry Screen Will appear if access code is required for p...

Page 5: ...pear if stage outputs 1 and 2 are disabled Stage 2 Differential Screen Enter a differential value for stage 2 This screen does not appear if stage out puts 1 and 2 are disabled Control Mode Screen Ent...

Page 6: ...by 1 degree for cooling Outdoor Air Sensor Screen Choose whether or not you are using an outdoor air sensor function To monitor only select no See setup instructions for dip switch settings which must...

Page 7: ...l be maintained and the fan will operate according to its unoc cupied setting The occupied LED will be lit when the unit is operating in the occupied mode The occupied schedule may be set utilizing th...

Page 8: ...ns or dis charge air reset function See Discharge Air Reset section for further programming options If NO is chosen the dis charge air is still monitored When the function is enabled a LOW LIMIT and H...

Page 9: ...ences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling stages are allowed to seque...

Page 10: ...roubleshooting section TROUBLESHOOTING No Display Check for 24 VAC on terminals 24 and 24 Check the cable connecting the cover to the base for a good connec tion Fan Does Not Come On The fan is on whe...

Page 11: ...a PC Additional monitoring is available by continually pressing the service key MON 72F 12 00 AM DISCHARGE AIR 55F OUTDOOR AIR OVERRIDE ON 178 MINUTES 75F HEAT STAGE 1 OFF MOD OUT 100 SERVICE STATUS O...

Page 12: ...ry default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 15 FAN SWITCHING The option to allow the occupant to change th...

Page 13: ...0 90 Occupied heating setpoint must be less than occupied cooling setpoint ADI 20 DegF Unoccupied heating setpoint 40 90 Unoccupied heating setpoint must be less than unoccupied cooling setpoint ADI 2...

Page 14: ...itch 0 No 1 Yes Enables System Switch button BD 5 Use of discharge air sensor 0 No 1 Yes Always monitored enables discharge air function BD 6 Use of outdoor air sensor 0 No 1 Yes BD 7 Enable smart rec...

Page 15: ...it 0 OK 1 Below Read only Discharge air function low limit BD 41 DI2 service status 0 OK 1 Check DI2 Read only DI2 Service NOTE 1 The Service status point represents general Check status if this is po...

Page 16: ...Rev 1000 R 2800 LAURA LANE IMIDDLETON WI 53562 I 800 288 9383 IFAX 608 836 9044 Iwww tcs basys com 16...

Reviews: