background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

2

POWERING THE SUPERSTAT

Superstats are powered from 24 VAC +/- 20%.
If wiring for communications, dedicated power must be 

used to power the Superstat. Several “S” Series thermo-

stats may be powered from the same transformer, provid-

ed that the transformer has sufficient power. (Superstats 

require 8 VA @ 24 VAC.)

Caution

:  Do not connect to 120 VAC.  When multiple 

TCS/Basys Controls devices are using a single 

transformer, the polarity of the power wiring must 

be maintained because all TCS devices are half-

wave rectified and have common return paths. 

When the Superstat is used as a stand-alone or wireless 

thermostat without communications, the unit transformer 

may be used to power it.  To do this, install a jumper 

between the “R” and “+24” terminals.  The “24-” terminal 

must then be connected to the common side of the unit 

transformer. 

Wiring                                     

The SZ1022, SZ1031, and SZ1035 use standard terminal 

designations for wiring.  See diagram below.

REMOTE TEMPERATURE SENSOR WIRING

Use 18 AWG shielded twisted-pair grounded at the sen-

sor mounting location. Sensor wiring runs of up to 250 

feet are attainable if properly shielded wire is used and 

the installation environment is free of electrical noise.  

Sensor wire should be kept at least five feet away from 

line voltage wiring.
The SZ1022 accepts two 2-wire remote sensors and the 

SZ1031 and the SZ1035 accept three. Consult the TS 

Series Temperature Sensor Submittal Data Sheet for 

a complete listing of packaging and application styles. 

When using TCS/Basys Controls three-wire sensors, use 

the black and red leads and either clip or twist off the 

white lead. Make sure that the dip switches are set for 

the sensors you are using.

Summary of Contents for SZ1022

Page 1: ...or limited with the use of an access code Fahrenheit or Celsius temperature display Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500...

Page 2: ...install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit transformer Wiring The SZ1022 SZ1031 and SZ1035 use standard terminal designation...

Page 3: ...sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1031 and SZ1035 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock...

Page 4: ...aud Rate Screen If using a PC to do programming all controllers on a network must be set to the same baud rate Choose between 2 4K 4 8K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and...

Page 5: ...4TH STAGE AS COOL 25 program setup ENABLE THIRD STAGE AS DISABLE 26 program setup HEAT STAGE 1 OFFSET 0F 27 program setup OCCUPIED COOL SETPOINT B 75F 16 program setup OCCUPIED COOL SETPOINT C 75F 17...

Page 6: ...etup ENABLE OUTDOOR AIR FUNCT YES 44 DISCHARGE AIR LOW LIMIT 45F ENABLE DISCHARGE AIR FUNCT YES program setup 41 program setup TIMECLOCK OUTPUT OCCUPIED CLOSED program setup 40 DISCHARGE AIR HIGH LIMI...

Page 7: ...CONDS DI3 USED FOR FILTER SERVICE program setup 50 program setup SET DI2 SETPOINT SHIFT 00F program setup 49 ENABLE SMART RECOVERY NO 52 program setup 51 program setup SET ACCESS CODE 248 55 MON 11 19...

Page 8: ...ed Times Screen Set hours and minutes of start and end times for up to two occupied periods Schedule Announcement Screen Announces the next screen Copy Schedule Screen Indicate whether or not to use t...

Page 9: ...such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to set the DI3 to external override and use the timed override button to put the...

Page 10: ...ment to the building load The offset value is the amount away from the setpoint a stage will turn off By assign ing a stage a value other than zero you anticipate that the residual heat or cooling in...

Page 11: ...35 also have a P I option Without enabling this option stages turn on and off based on temperature vs setpoint alone as described above By enabling this option you allow a time factor to be added This...

Page 12: ...support you may be able to use the on board adjustment pots Refer to the Thermostat Sensor Calibration Tech Bulletin 1005 for details setpoint adjustment limits Change this to 20 F 11 1 C Press the P...

Page 13: ...the override is active and if so how many minutes remain ing service status MON 11 19 01 12 00 AM 72F service status SERVICE STATUS OK 1 service status OUTDOOR AIR TEMP 75F 3 service status DISCHARGE...

Page 14: ...allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedul...

Reviews: