background image

reset ratio factor. This  is the number of degrees that 

the discharge air setpoint is raised when the room tem-

perature falls below the heating setpoint by 1 degree if 

the analog output is set for heating, or the number of 

degrees that the discharge air setpoint is lowered when 

the room temperature rises above the cooling setpoint by 

1 degree if the analog output is set for cooling.

oUtdooR AiR temPeRAtURe SenSing

The SZ1041A accepts a remote outdoor temperature 

sensor for monitoring purposes. (See setup instructions 

for dipswitch placement for this option.) 
Choose YES in programming screen #37 only if you are 

using an outdoor air sensor and you want to enable the 

outdoor air heating and cooling lockout functions. If NO 

is chosen, the outdoor air is still monitored.
When the function is enabled, COOLING LOCKOUT 

TEMP and HEATING LOCKOUT TEMP are entered 

in steps #38 and #39. If the outdoor air temperature 

falls below the COOLING LOCKOUT TEMP, all cooling 

stages will be locked out and will remain locked out until 

the outdoor air temperature rises 2° above the lockout 

temperature. If the outdoor air temperature rises above 

the HEATING LOCKOUT TEMP, all heating stages will 

be locked out and will remain locked out until the outdoor 

air temperature falls 2° below the lockout temperature. 
The outdoor air span is -40 to 160 °F (-40.0 to 71.1 °C).

FAn PRoving

The SZ1041A allows DI1 to be set for fan proving to pro-

tect equipment on fan failure. To utilize this, a pressure 

or current switch is required, which indicates when the 

fan is running. If the thermostat turns on the FAN, and 

DI1 is not closed after thirty seconds, the system will go 

to OFF, disabling all outputs, the fan LED will turn off 

and the service LED will be lit until the system is manu-

ally reset by switching the system to a mode other than 

OFF.  

di2 SetPoint ShiFt

The SZ1041A allows 

DI2 to be set for set-

point shift for energy 

demand setback. This 

is enabled by setting 

DI2 to the MONITOR 

mode. A digital contact 

that closes when set-

back is needed should 

be wired into DI2. You 

may specify a number 

of degrees such that, 

when the thermostat is 

operating in the occu-

pied mode, and DI2 is closed, the heating setpoint will 

be lowered this number of degrees, and the cooling set-

point will be raised this number of degrees. The fan will 

continue to operate according to its occupied setting. If 

you are using DI2 as monitor for another purpose, make 

sure to set the setpoint shift value to zero.

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

10

StAge oUtPUt PARAmeteRS

The SZ1041A will control up to two stages of either heat-

ing or cooling. The SZ1041A will control two stages of 

heating and two stages of cooling.
For each stage, you may specify an offset and a differ-

ential value. The offset value is the amount away from 

the setpoint a stage will turn off. By assigning a stage a 

value other than zero, you “anticipate” that the residual 

heat or cooling in the duct or the other stages will bring 

the temperature back to setpoint. In most cases, the first 

stage is set to zero. The differential value is the difference 

between the on and off points. 
Unlike most other multi-stage programmable thermostats, 

the Superstat allows independent adjustments of "offsets" 

and "differentials" for stages of heating and cooling.  The 

offset settings can be viewed as setpoints for the second 

and third stages and are programmed in the Superstat in 

the number of degrees (i.e. 1,2,3…) beyond the heating 

and cooling setpoints (temperatures to be maintained).  
The differential for each stage can be viewed as the 

"anticipator" function used in mechanical thermostats.

P+i oPtion

The SZ1041A also have a P+I option. Without enabling 

this option, stages turn on and off based on temperature 

vs. setpoint alone, as described above. By enabling this 

option, you add a time factor to anticipate heating and 

cooling. 

AnAlog oUtPUt PARAmeteRS

Use programming steps #48 through #58 to program the 

operating parameters for the analog output. Select wheth-

er the analog output is set for heating, cooling or econo-

mizer. Select direct or reverse action. Select whether you 

want the analog output to modulate from 4 to 20mA or 

0 to 20mA. Select the unoccupied action ("20mA or 0 / 

4mA" will hold the analog output device open or closed 

during unoccupied times. "Modulating" will modulate the 

analog output device to maintain the unoccupied heating 

or cooling setpoint.). Enter a proportional band (throttling 

range) in degrees. Enter a setpoint offset in degrees. 

heat

Setpoint

Cool

Setpoint

on

on

on

on

oFF

oFF

oFF

oFF

differential

differential

offset

offset

differential

differential

 4                         20

 4                         20

 4                         20

 4                         20

 4                         20

 4                         20

P

Z

o

n

e

 

T

e

m

p

Output

   (m A)

P

Output

   (m A)

diReCt ACting

ReveRSe ACting

P

P

Output

   (m A)

Output

   (m A)

Z

o

n

e

 

T

e

m

p

P

P

Output

   (m A)

Output

   (m A)

P

P

Z

o

n

e

 

T

e

m

p

CSP

CSP

hSP

hSP

CSP

CSP

hSP

hSP

Summary of Contents for SZ1041A

Page 1: ...l time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 4 Setting Clock Schedule 8 Operation 9 Checkout Troubleshooting 12 LED Description 14 Limiting Occupant Access 15 User s Guide 15 Mounting The SZ1041A is designed for wall...

Page 2: ...sensors Consult the TS Series Temperature Sensor Submittal Data sheet for a complete listing of packaging and application styles When using TCS Basys Controls three wire sensors use the black and red leads and either clip or twist off the white lead Make sure that the dip switches are set for the sensors you are using Powering the SZ1041A Superstats are powered from 24 VAC 20 If wiring for communi...

Page 3: ... Using remote room sensor with both discharge and outdoor air sensors KEypad Access The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of programming and or to set the clock and sched ule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in programming The fan and sys...

Page 4: ...re indication System Access Screen Choose whether or not to enable user s access to the sys tem switch to set the system mode System Mode Screen Choose from AUTO HEAT COOL or OFF for system mode In the OFF mode all outputs are off Fan Access Screen Choose whether or not to enable the user s access to the fan switch to set the occupied fan mode Occupied Fan Mode Screen Choose between ON continuous ...

Page 5: ... if heat stage 2 is enabled as heat Heat Stage 2 Differential Screen Enter a differential value for heat stage 2 This screen only appears if heat stage 2 is enabled Cool Stage 1 Offset Screen Enter an offset value for cool stage 1 First stage is normally 0 offset Cool Stage 1 Differential Screen Enter a differential value for cool stage 1 Cool Stage 2 Offset Screen Enter an offset value for cool s...

Page 6: ...isabled AO CONTROL BASED ON SPACE 48 program setup ENABLE HEATING LOW LIMIT YES 49 program setup ENABLE MOD OUT 1 MIN MAX POS YES 54 program setup MOD OUT 1 MIN POS 10 55 program setup MOD OUT 1 MAX POS 99 56 program setup Reset Ratio Factor Screen Enter a reset ratio factor This is the number of degrees that the discharge air setpoint is raised when the space tempetature falls by 1 degree for hea...

Page 7: ...cess Screen Choose whether or not a code will be required to enter programming setup A dipswitch option to lock out access altogether is also avail able Clock and Schedule Access Screen Choose whether or not a code will be required to enter clock and schedule setup A dipswitch option to lock out access alto gether is also available Access Code Screen Enter an access 0 to 255 code that will be used...

Page 8: ... next screen does not appear Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Holiday Announcement Screen Announces the next screen Holidays 1 Screen Set holiday peri ods 1 through 12 month date and dura tion for the periods that will follow the holiday 1...

Page 9: ...in the occupied mode whenever the DI3 contact is closed When using this option the timed override may still be activated The software allows you to override the thermostat by putting the override parameter into the remote mode and thus disabling the timed override Setback and Override Applications In most applications it is desired to maintain a regular schedule and allow timed override with the b...

Page 10: ...ue to operate according to its occupied setting If you are using DI2 as monitor for another purpose make sure to set the setpoint shift value to zero R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 10 Stage Output Parameters The SZ1041A will control up to two stages of either heat ing or cooling The SZ1041A will control two stages of heating and two stages of co...

Page 11: ...41A has delays built into the programming sequences to protect equipment The fan has a mini mum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling devices are allowed to sequence on and remain on for 2 minutes after the heating or cooling devices sequence off Each stage has a minimum on and off time of two minutes There is a ...

Page 12: ... that the top LED is lit If not press the OVERRIDE button The LED should light up 6 Take note of the current temperature reading Press DIGITAL APPLICATION LED SERVICE SCREEN CONTROL SENSOR OR INPUT INDICATION DI STATUS SCREEN PROVIDED DEVICE NEEDED DI1 Fan Proving YES CHECK FAN YES turns system mode to off Differential FAN OK requires manual re start pressure or or FAIL set system to auto current ...

Page 13: ...ystem switch button and the service status button simultaneously the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five degrees The fan will come on The heating stage s will sequence on after 30 seconds 7 Press the cooler down button until the heating set point is one degr...

Page 14: ...ir limit has been reached when the fan interlock has indi cated failure or when the filter service or service input are closed PROGRAM DATA This LED will be lit when the thermostat is within the programming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is available by continually pressing the service key Main Monitoring Screen Press the service bu...

Page 15: ...on to allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 Setting Clock Schedule The ability to set the clock and schedule is allowed by factory default An access code may be required as set in programming step 64 or access may be denied altogether using dipswitches described in the setup sec tion Programming The ...

Reviews: