background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

11

(This is a value below the heating setpoint or above 

the cooling setpoint where the analog output begins to 

modulate.)

eConomiZeR oPeRAtion

The analog output on the SZ1041A can be used to con-

trol an economizer. Both outdoor air and discharge air 

temperature sensors are needed to accomplish this. 

note:

 The discharge air sensor may be installed in the 

discharge air section or in the mixed air section. This 

instruction as well as product literature refers to a dis-

charge air sensor, regardless of where it is mounted.
During occupied time, the outside air dampers are held 

at a minimum position, entered in programming step 

#46, until economizer operation is enabled. During unoc-

cupied time, the outside air dampers are closed.
In programming screen #42, you are asked to enter an 

outdoor air setpoint. The outdoor air temperature must 

fall below this setpoint before economizer operation will 

be enabled. A call for cooling is also required to enable 

economizer operation. A typical value is 65°F.
In programming screen #43b, you are asked to enter a 

discharge air setpoint. The discharge air temperature will 

be controlled to this setting by modulating the outdoor 

air dampers, when economizer operation is enabled. In 

programming screen #44, you are asked to enter a dis-

charge air low limit setpoint. If the discharge air falls to 

this setpoint, the outside air dampers will close.
A proportional band (throttling range), whether you want 

the analog output to modulate from 4 to 20mA or 0 to 

20mA, and direct or reverse action must also be pro-

grammed.

SmARt ReCoveRy

“Smart Recovery” may be enabled. It ramps the setpoint 

4°F/hr. when going from the unoccupied  mode to the 

occupied mode. At the beginning of the occupied mode, 

the occupied setpoint will be reached, many times with-

out the need for the second stage to come on. This fea-

ture is automatically disabled when DI3 is set to external 

time clock. 

BUilt-in delAyS

The SZ1041A has delays built into the programming 

sequences to protect equipment. The fan has a mini-

mum on and off time of 30 seconds. When the fan is 

in AUTO or COOL mode, it will come on 30 seconds 

before the heating or cooling devices are allowed to 

sequence on, and remain on for 2 minutes after the 

heating or cooling devices sequence off. Each stage has 

a minimum on and off time of two minutes. There is a 

minimum of 2 minutes between when one stage turns 

on until the next stage is allowed to turn on, as well as 

when one stage turns off until the next stage is allowed 

to turn off. 
Delay on occupied, see delay on powerup.

delAy on PoWeRUP

The SZ1041A has an adjustable delay on powerup. 

When several thermostats are used at one location, 

and the power goes out, most thermostats turn all of the 

units back on at the same time on regain of power, cre-

ating a peak. The thermostat allows you to set a value, 

in seconds, where no outputs are allowed to turn on for 

that length of time on powerup. Setting each unit to a 

different delay allows you to soft start your system, and 

thus prevent this peak. This delay can also be applied to 

the start of occupied time.

dAylight SAvingS time

Beginning in 2007, Daylight Saving Time (DST) in the 

U.S. will be extended by having an earlier change to 

DST in spring and a delay in switching back to standard 

time in fall. However, this change may only be temporary, 

as this "new" schedule is only in effect for a 2 year trial 

period. After that, the DST schedule may revert back, 

stay the same, or be something completely different. 

Products shipped starting in 2007 with firmware ver-

sion 1.5 or higher accommodate the new DST schedule. 

Products shipped starting in 2008 with firmware version 

2.0 or higher accommodate the new DST schedule and 

have the ability to be programmed to accommodate any 

future schedules that may be used. Should the sched-

ule change and you need to customer program the DST 

start and end dates, simply enable the "Daylight Savings 

Time" option within the software and enter the starting 

month + week and the ending month + week.

 4                         20

 4                         20

 4                         20

 4                         20

 4                         20

 4                         20

P

Z

o

n

e

 

T

e

m

p

Output

   (m A)

P

Output

   (m A)

diReCt ACting

ReveRSe ACting

P

P

Output

   (m A)

Output

   (m A)

Z

o

n

e

 

T

e

m

p

P

P

Output

   (m A)

Output

   (m A)

P

P

Z

o

n

e

 

T

e

m

p

CSP

CSP

hSP

hSP

CSP

CSP

hSP

hSP

Summary of Contents for SZ1041A

Page 1: ...l time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 4 Setting Clock Schedule 8 Operation 9 Checkout Troubleshooting 12 LED Description 14 Limiting Occupant Access 15 User s Guide 15 Mounting The SZ1041A is designed for wall...

Page 2: ...sensors Consult the TS Series Temperature Sensor Submittal Data sheet for a complete listing of packaging and application styles When using TCS Basys Controls three wire sensors use the black and red leads and either clip or twist off the white lead Make sure that the dip switches are set for the sensors you are using Powering the SZ1041A Superstats are powered from 24 VAC 20 If wiring for communi...

Page 3: ... Using remote room sensor with both discharge and outdoor air sensors KEypad Access The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of programming and or to set the clock and sched ule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in programming The fan and sys...

Page 4: ...re indication System Access Screen Choose whether or not to enable user s access to the sys tem switch to set the system mode System Mode Screen Choose from AUTO HEAT COOL or OFF for system mode In the OFF mode all outputs are off Fan Access Screen Choose whether or not to enable the user s access to the fan switch to set the occupied fan mode Occupied Fan Mode Screen Choose between ON continuous ...

Page 5: ... if heat stage 2 is enabled as heat Heat Stage 2 Differential Screen Enter a differential value for heat stage 2 This screen only appears if heat stage 2 is enabled Cool Stage 1 Offset Screen Enter an offset value for cool stage 1 First stage is normally 0 offset Cool Stage 1 Differential Screen Enter a differential value for cool stage 1 Cool Stage 2 Offset Screen Enter an offset value for cool s...

Page 6: ...isabled AO CONTROL BASED ON SPACE 48 program setup ENABLE HEATING LOW LIMIT YES 49 program setup ENABLE MOD OUT 1 MIN MAX POS YES 54 program setup MOD OUT 1 MIN POS 10 55 program setup MOD OUT 1 MAX POS 99 56 program setup Reset Ratio Factor Screen Enter a reset ratio factor This is the number of degrees that the discharge air setpoint is raised when the space tempetature falls by 1 degree for hea...

Page 7: ...cess Screen Choose whether or not a code will be required to enter programming setup A dipswitch option to lock out access altogether is also avail able Clock and Schedule Access Screen Choose whether or not a code will be required to enter clock and schedule setup A dipswitch option to lock out access alto gether is also available Access Code Screen Enter an access 0 to 255 code that will be used...

Page 8: ... next screen does not appear Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Holiday Announcement Screen Announces the next screen Holidays 1 Screen Set holiday peri ods 1 through 12 month date and dura tion for the periods that will follow the holiday 1...

Page 9: ...in the occupied mode whenever the DI3 contact is closed When using this option the timed override may still be activated The software allows you to override the thermostat by putting the override parameter into the remote mode and thus disabling the timed override Setback and Override Applications In most applications it is desired to maintain a regular schedule and allow timed override with the b...

Page 10: ...ue to operate according to its occupied setting If you are using DI2 as monitor for another purpose make sure to set the setpoint shift value to zero R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 10 Stage Output Parameters The SZ1041A will control up to two stages of either heat ing or cooling The SZ1041A will control two stages of heating and two stages of co...

Page 11: ...41A has delays built into the programming sequences to protect equipment The fan has a mini mum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling devices are allowed to sequence on and remain on for 2 minutes after the heating or cooling devices sequence off Each stage has a minimum on and off time of two minutes There is a ...

Page 12: ... that the top LED is lit If not press the OVERRIDE button The LED should light up 6 Take note of the current temperature reading Press DIGITAL APPLICATION LED SERVICE SCREEN CONTROL SENSOR OR INPUT INDICATION DI STATUS SCREEN PROVIDED DEVICE NEEDED DI1 Fan Proving YES CHECK FAN YES turns system mode to off Differential FAN OK requires manual re start pressure or or FAIL set system to auto current ...

Page 13: ...ystem switch button and the service status button simultaneously the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five degrees The fan will come on The heating stage s will sequence on after 30 seconds 7 Press the cooler down button until the heating set point is one degr...

Page 14: ...ir limit has been reached when the fan interlock has indi cated failure or when the filter service or service input are closed PROGRAM DATA This LED will be lit when the thermostat is within the programming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is available by continually pressing the service key Main Monitoring Screen Press the service bu...

Page 15: ...on to allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 Setting Clock Schedule The ability to set the clock and schedule is allowed by factory default An access code may be required as set in programming step 64 or access may be denied altogether using dipswitches described in the setup sec tion Programming The ...

Reviews: