background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

12

Checkout & Troubleshooting      

CheCKoUt
note:

 The fan has a minimum on and off time of 30 

seconds. The heating and cooling stages have a mini-

mum on and off time of 2 minutes. 
You may verify the status of heating and cooling and fan 

in monitoring screens 5, 6, and 7, which are accessed 

by pressing the SERVICE STATUS button. 
1.  Verify all wiring prior to powering the thermostat.
2.  Turn power on. The thermostat will display a momen-

tary screen with the model number, and then the 

main monitoring screen with the time, day, date and 

current temperature. 

3.  Press the PROGRAM SETUP button until you reach 

the screen # 20 which allows you to set the occupant 

setpoint adjustment limits. Change this to +/-20 °F 

(11.1 °C). Press the PROGRAM SETUP button once 

more to store the change. Then press the SERVICE 

STATUS button once to exit the programming. 

4.  Press the FAN SWITCH button to access the fan 

mode and change the mode to AUTO. Press the 

FAN SWITCH button once more to store the change.  

Press the SYSTEM SWITCH button to access the 

system mode and change the mode to AUTO. Press 

the SYSTEM SWITCH button once more to store the 

change.  

5.  Verify that the thermostat is operating in the occupied 

mode by making sure that the top LED is lit. If not, 

press the OVERRIDE button. The LED should light 

up. 

6.  Take note of the current temperature reading. Press 

 DIGITAL 

APPLICATION 

LED 

SERVICE SCREEN 

CONTROL 

SENSOR OR  

 INPUT 

 

INDICATION? 

(DI STATUS SCREEN) 

PROVIDED 

DEVICE NEEDED

 
  DI1 

Fan Proving 

YES 

CHECK FAN,  

YES - turns system mode to "off" 

Differential  

    

 

 

FAN OK 

— requires manual re-start  

pressure or 

 

 

 

 

 

or FAIL 

(set system to auto) 

current switch 

  DI1 

Low Temp Alarm 

YES 

LOW TEMP ALARM 

NO 

Dry contact, switch 

 

 

 

 

(Also shows LOW TEMP ALARM 

 

 

 

 

on main screen)

  DI1 

Equipment 

NO 

OK 

NO 

Dry contact, switch.  Any type  

 

 

Monitoring 

 

(DI1 OPEN or CLOSED) 

 

for monitoring and indication 

 
  D12 

Economizer 

NO 

OK 

YES, Limits AO1 to min position 

Enthalpy Sensor, Swtich 

 

 

 

 

(Shows ECON ON or OFF) 

when ECON OFF 

 
  DI2 

Filter Service 

YES 

OK 

NO 

Dry contact, switch.  Any type  

 

 

 

 

(OK or Check Filter) 

 

  DI2 

Monitor with 

NO 

OK 

YES - shifts setpoint by  

Dry contact, switch. 

 

 

setpoint shift 

 

(DI2 OPEN or CLOSED) 

programmed amount  

   

 

  DI3 

Filter Service 

YES 

OK or CHECK FILTER 

NO 

Differential pressure switch 

 

 

 

 

(FILTER OK or CHECK)

  DI3 

External Occupancy Override

 

NO 

OK 

YES - switches to occupied mode  

Dry contact such as twist  

 

 

 

 

(EXT OVER ON or OFF) 

as long as contact is made* 

timer, light switch, etc.

  DI3 

External Time Clock Input 

NO 

OK 

YES -input overrides thermostat  

Dry contact;  

 

 

 

YES 

(EXT TIMECLOCK ON or OFF) 

occupancy program 

external time clock 

 

 

 

Occupied? 

 

 

(TCS part SL1001a)

Digital Input Summary Table

*See delay on occupied.

LIMIT SETPOINT

ADJUST  +/-:        5F

MON 

08-08-08

12:00AM 

72F

* SZ1041 * 

 TCS V2.07 (c)

Summary of Contents for SZ1041A

Page 1: ...l time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 4 Setting Clock Schedule 8 Operation 9 Checkout Troubleshooting 12 LED Description 14 Limiting Occupant Access 15 User s Guide 15 Mounting The SZ1041A is designed for wall...

Page 2: ...sensors Consult the TS Series Temperature Sensor Submittal Data sheet for a complete listing of packaging and application styles When using TCS Basys Controls three wire sensors use the black and red leads and either clip or twist off the white lead Make sure that the dip switches are set for the sensors you are using Powering the SZ1041A Superstats are powered from 24 VAC 20 If wiring for communi...

Page 3: ... Using remote room sensor with both discharge and outdoor air sensors KEypad Access The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of programming and or to set the clock and sched ule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in programming The fan and sys...

Page 4: ...re indication System Access Screen Choose whether or not to enable user s access to the sys tem switch to set the system mode System Mode Screen Choose from AUTO HEAT COOL or OFF for system mode In the OFF mode all outputs are off Fan Access Screen Choose whether or not to enable the user s access to the fan switch to set the occupied fan mode Occupied Fan Mode Screen Choose between ON continuous ...

Page 5: ... if heat stage 2 is enabled as heat Heat Stage 2 Differential Screen Enter a differential value for heat stage 2 This screen only appears if heat stage 2 is enabled Cool Stage 1 Offset Screen Enter an offset value for cool stage 1 First stage is normally 0 offset Cool Stage 1 Differential Screen Enter a differential value for cool stage 1 Cool Stage 2 Offset Screen Enter an offset value for cool s...

Page 6: ...isabled AO CONTROL BASED ON SPACE 48 program setup ENABLE HEATING LOW LIMIT YES 49 program setup ENABLE MOD OUT 1 MIN MAX POS YES 54 program setup MOD OUT 1 MIN POS 10 55 program setup MOD OUT 1 MAX POS 99 56 program setup Reset Ratio Factor Screen Enter a reset ratio factor This is the number of degrees that the discharge air setpoint is raised when the space tempetature falls by 1 degree for hea...

Page 7: ...cess Screen Choose whether or not a code will be required to enter programming setup A dipswitch option to lock out access altogether is also avail able Clock and Schedule Access Screen Choose whether or not a code will be required to enter clock and schedule setup A dipswitch option to lock out access alto gether is also available Access Code Screen Enter an access 0 to 255 code that will be used...

Page 8: ... next screen does not appear Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Holiday Announcement Screen Announces the next screen Holidays 1 Screen Set holiday peri ods 1 through 12 month date and dura tion for the periods that will follow the holiday 1...

Page 9: ...in the occupied mode whenever the DI3 contact is closed When using this option the timed override may still be activated The software allows you to override the thermostat by putting the override parameter into the remote mode and thus disabling the timed override Setback and Override Applications In most applications it is desired to maintain a regular schedule and allow timed override with the b...

Page 10: ...ue to operate according to its occupied setting If you are using DI2 as monitor for another purpose make sure to set the setpoint shift value to zero R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 10 Stage Output Parameters The SZ1041A will control up to two stages of either heat ing or cooling The SZ1041A will control two stages of heating and two stages of co...

Page 11: ...41A has delays built into the programming sequences to protect equipment The fan has a mini mum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling devices are allowed to sequence on and remain on for 2 minutes after the heating or cooling devices sequence off Each stage has a minimum on and off time of two minutes There is a ...

Page 12: ... that the top LED is lit If not press the OVERRIDE button The LED should light up 6 Take note of the current temperature reading Press DIGITAL APPLICATION LED SERVICE SCREEN CONTROL SENSOR OR INPUT INDICATION DI STATUS SCREEN PROVIDED DEVICE NEEDED DI1 Fan Proving YES CHECK FAN YES turns system mode to off Differential FAN OK requires manual re start pressure or or FAIL set system to auto current ...

Page 13: ...ystem switch button and the service status button simultaneously the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five degrees The fan will come on The heating stage s will sequence on after 30 seconds 7 Press the cooler down button until the heating set point is one degr...

Page 14: ...ir limit has been reached when the fan interlock has indi cated failure or when the filter service or service input are closed PROGRAM DATA This LED will be lit when the thermostat is within the programming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is available by continually pressing the service key Main Monitoring Screen Press the service bu...

Page 15: ...on to allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 Setting Clock Schedule The ability to set the clock and schedule is allowed by factory default An access code may be required as set in programming step 64 or access may be denied altogether using dipswitches described in the setup sec tion Programming The ...

Reviews: