AO1 MODE AS:
HEAT
41.
program
setup
program
setup
DSCHARGE AIR
PROP BAND: 010F
45.
program
setup
OUTDOOR DAMPER
MIN POSITION: 10%
46.
program
setup
DSCHARGE AIR
LOW LIMIT 040F
44.
program
setup
DSCHARGE AIR
SETPOINT:
055F
43.
program
setup
OUTDOOR AIR ECON
SETPOINT:
068F
42.
program
setup
AO1 OUTPUT
RANGE: 4-20 MA
47.
heating lockout Screen.
Enter an outdoor
air heating lockout temperature. This screen
will not appear if the outdoor air sensor functi-
ion is disabled.
discharge Air Sensor Function Screen.
Choose whether or not you are using a dis-
charge air sensor function. To monitor only,
select NO. See setup instructions for dip-
switch settings which must also be set.
Ao1 mode Selection Screen:
Choose if AO1 is HEAT, COOL or ECON.
outdoor Air economizer Setpoint Screen.
Set the outdoor air setpoint. This screen will
not appear if the discharge air sensor function
is disabled.
discharge Air Setpoint Screen.
Set the
discharge air setpoint. This screen will not
appear if the discharge air sensor function is
disabled.
discharge Air low limit Screen.
Enter a
discharge air low limit value. This screen will
not appear if the discharge air sensor function
is disabled.
discharge Air Proportional Band Screen.
Set the discharge air proportional band or
throttling range. This screen will not appear if
the discharge air sensor function is disabled.
outdoor damper min. Position Screen.
Set
the minimum damper position. This screen
will not appear if the discharge air sensor
function is disabled.
Ao1 output Screen.
Choose whether the
modulating output range will be 0-20 mA or
4-20 mA. This screen will not appear if the
discharge air sensor function is disabled.
modulating output 1 Control Screen
.
Choose whether to control based on
DISCHARGE air reset of SPACE tempera-
ture.
enable heating low limit Screen.
Choose
whether to enable Heating Low temperature
limit. Only appears if AO1 mode is HEAT.
discharge Air Setpoint Screen.
Set the
discharge air setpoint. This screen will not
appear if the discharge air sensor function is
disabled.
AO CONTROL BASED
ON: SPACE
48.
program
setup
ENABLE HEATING
LOW LIMIT: YES
49.
program
setup
ENABLE MOD OUT 1
MIN/MAX POS: YES
54.
program
setup
MOD OUT 1
MIN POS: 10%
55.
program
setup
MOD OUT 1
MAX POS: 99%
56.
program
setup
Reset Ratio Factor Screen.
Enter a reset
ratio factor. This is the number of degrees
that the discharge air setpoint is raised when
the space tempetature falls by 1 degree for
heating, or the number of degrees that the
discharge air setpoint is lowered when the
space temperature rised by 1 degree for cool-
ing.
modulating output Proportional Band
Screen.
Enter the number of degrees away
from the setpoint that the valves or damper
will be fully open.
Analog output Setpoint offset Screen.
Enter a setpoint offset. This is a value below
the heating setpoint or above the cooling
setpoint where the analog output begins
modulate.
enable min/max PoS Screen.
Choose
whether to enable min/max mod out 1 control.
min Position Screen.
Set the minimum posi-
tion for analog output 1.
max Position Screen.
Set the maximum
position for analog output 1.
modulating output 1 Action Screen
.
Choose whether the output will be direct
reverse acting.
Ao1 output Range Screen
. Choose whether
the modulating output range will be 0-20 mA
or 4-20 mA.
di1 Choice Screen.
Choose DI1 as FAN
PROVING, LOW TEMP ALARM or a
MONITOR point. Select MONITOR if unused.
di2 Choice Screen.
Choose DI2 as ECON,
FILTER SERVICE or MONITOR. Select
MONITOR if unused.
di2 Shift Screen.
Enter the setpoint shift
value. This screen will only appear if DI2 is
set to MONITOR
di3 Choice Screen.
Choose FILTER SERVICE,
EXTernal OVERRIDE, or EXTernal TIME
CLOCK. Select EXTernal OVERRIDE if unused.
AO 1 CONTROL
ACTION: DIRECT
57.
program
setup
AO1 OUTPUT RANGE
RANGE: 4-20 MA
58.
program
setup
program
setup
DI1 USED FOR
MONITOR
59.
program
setup
DI2 USED FOR
MONITOR
60.
program
setup
DI3 USED FOR:
FILTER SERVICE
62.
program
setup
SET DI2 SETPOINT
SHIFT:
00F
61.
Not
e:
Only appear if A
O1 mode is EC
ON.
MOD OUT 1 SET P.
OFFSET: 00F
53.
program
setup
DISCHARGE AIR
SETPOINT: 55F
50.
program
setup
Not
e:
Only appear if A
O1 mode is Hea
t of C
ool
.
program
setup
ENABLE DISCHARGE
AIR FUNCT.? YES
40.
program
setup
HEATING LOCKOUT
TEMP:
070F
39.
RESET RATIO
FACTOR: 2F
51.
program
setup
MOD OUT 1
BAND: 05F
52.
program
setup
Not
e:
Only appear if A
O1 mode is Hea
t of C
ool
.