Scope of delivery
1 x FBI4500-0100
Product information
Safety instructions
General safety regulations
!
Attention! Mounting, installation, commissioning and repair of electronic devices have
to be carried out only by qualified electricians. The latest accident prevention regulati-
ons must be observed.
For working on systems with main connection of 230 V alternating voltage, the safety re-
quirements according to DIN VDE 0100 must be observed.
When installing TCS:BUS
®
systems, the general safety regulations for telecommunication
systems according to VDE 0800 must be observed. Inter alia:
separated conduit of heavy current and low current lines,
minimum distance of 10 cm in case of a common conduit,
use of separators between heavy and low current lines within shared cable ducts,
use of standard communication lines, e.g. J-Y (St) Y with a diamter of 0.8 mm,
exisiting lines (modernisation) with deviating cross-sections can be used in compliance
with the loop resistance.
Installation
– protective measures
!
With suitable measures to protect against lightning, it has to be ensured that a voltage
of 32 V DC is not exceeded at the connections a, b, E, P, M, V1, V2, V, ┴, +, −.