background image

HR150, 200; ER150, 200 FRESH AIR VENTILATION SYSTEMS

5

68-0269

Sizing 

There are several methods that can provide satisfactory 

results for sizing a ventilator to provide adequate ventilation 

for a home. The ASHRAE Standard 62-1989 Ventilation for 

Acceptable Indoor Air Quality suggests the following:

— .35 air changes per hour (ach) but not less than 15 cfm per 

person for living areas = house size (sq ft) • ceiling height 

(ft) / 60 (min) •.35 (ach)

Example: 

= 2000 sq ft • 8 ft / 60 min •.35 ach = 93 cfm

— 50 cfm intermittent or 20 cfm continuous capacity for 

bathrooms

Example: 

50 cfm intermittent • 3 bathrooms = 150 cfm

20 cfm continuous • 3 bathrooms = 60 cfm

— 100 cfm intermittent or 25 cfm continuous capacity for 

kitchens

Example:

100 cfm intermittent • 1 kitchen = 100 cfm

25 cfm continuous • 1 kitchen = 25 cfm

Option 1: Fresh Air Ventilation System provides continuous 

fresh air supply of 93 cfm, and intermittent capacity for 

bathrooms of 150 cfm. A separate 100 cfm exhaust fan is 

used for the range hood.

Supply air flow required = 93 cfm

Exhaust air flow required = 150 cfm

Any Total Comfort System ventilation unit provides suitable 

ventilation capacity. See Fig. 1.

Option 2: Fresh Air Ventilation System provides continuous 

fresh air supply of 93 cfm, intermittent exhaust capacity for 

bathrooms of 150 cfm, and continuous kitchen ventilation of 

50 cfm.

Supply air flow required = 93 cfm

Exhaust air flow required = 200 cfm

Total Comfort System HR200/ER200 have the exhaust 

capacity required to meet the ventilation needs of this 

application. See Fig. 1.

Mounting Position and Location

The HR150/ER150 and HR200/ER200 can be suspended 

from exposed ceiling joists or the ceiling surface, or floor 

mounted. The ventilator must be level for the drains to 

function properly.

• Locate the fresh air intake 6 ft (2m) or more from the stale 

air exhaust to avoid re-entry of the exhaust air.

• Locate the ventilator where the length of ducting required is 

minimal.

Install the HR150/ER150 and HR200/ER200 in a conditioned 

space using these guidelines:

• Pipe the drain line from the ventilator to a drain.

• Use an existing electrical outlet with the appropriate 

current rating (or install one) close to the ventilator power 

cord.

• Allow space for the drain line by placing the ventilator at 

least 10 in. (254 mm) off the floor.

• For access and removal of the ventilator core, allow at 

least 25 in. (635 mm) of open space in front of the unit.

Ducting

Ducting between the ventilator and the outdoors must be 

insulated and have a continuous air vapor barrier. See Fig. 5.

IMPORTANT

All ducting to the outdoors must be terminated above 

anticipated snow lines and be fitted with a weather 

cap that incorporates bird screening.

Fig. 4. Sealing insulated duct terminations.

Design and installation of ductwork must be in accordance 

with standard HVAC practice to deliver required quantities of 

fresh air to the temperature-controlled space and exhaust 

equivalent quantities of room air to the outside.

Keep intake and exhaust duct runs as short as possible with 

few bends or elbows.

• Keep duct sizes as large as possible throughout the 

installation.

• Use a 6 in. diameter round duct for all connections to and 

from the ventilator.

• Separate outside intake and exhaust vents by at least 6 ft 

(2m).

NOTES:

Do not locate the fresh air vent where it blows 

directly onto occupants or the thermostat.

Do not locate the fresh air intake close to known 

sources of pollutants such as automobile exhaust, 

a dryer vent or chimney smoke.

• Ducting the supply outlet and/or the exhaust inlet of the 

ventilator to the return air plenum of the air handler is an 

excellent way to distribute fresh air and exhaust stale air 

from all parts of the house, while reducing installation 

costs. When choosing this method, balance the ventilator 

when the air handler is running and interlock the ventilator 

so that it can run only when the air handler runs. See 

Fig. 6. An alternate method is to balance the ventilator 

when the air handler is not running and let the ventilator 

run whether the air handler is running or not, see Fig. 7. An 

independent installation is shown in Fig. 8.

INSULATED 
FLEX DUCT 

COLLAR ON 
VENTILATOR

SEAL INTERIOR LINING OF 
FLEX DUCT TO INSIDE COLLAR

SEAL OUTER LINING OF FLEX 
DUCT TO OUTER COLLAR

M6557

Summary of Contents for HR150

Page 1: ...verride Integral balancing dampers for quick installation Provides ventilation that helps contractors meet ASHRAE 62 89 4 speed fan control Automatic economical built in frost control for operation to...

Page 2: ...0 cfm aluminum core manual control and frost control HR200B 200 cfm aluminum cross flow core manual con trol and frost control ER150B 150 cfm moisture transferring core manual con trol and frost contr...

Page 3: ...ET SUPPLY AIR FLOW HR150 ER150 VENTILATION PERFORMANCE 0 GROSS SUPPLY GROSS EXHAUST 0 0 2 0 4 0 6 0 8 1 1 2 1 4 1 6 1 8 2 50 150 100 200 250 300 350 400 M6562A cfm L s n x 0 4719 in wg Pa n x 248 8 1...

Page 4: ...at is transferred from one airstream to the other as the air passes through the opposite sides of the heat transfer core See Fig 4 Fig 3 Duct connections and airflow 14 3 4 375 31 787 19 483 SERVICE C...

Page 5: ...ain line from the ventilator to a drain Use an existing electrical outlet with the appropriate current rating or install one close to the ventilator power cord Allow space for the drain line by placin...

Page 6: ...IALLY BASEMENTS FORCED AIR FURNACE COMBUSTION OR ELECTRIC M20854 RETURN AIR OUTDOORS NOTES 1 2 3 4 FURNACE BLOWER NEED NOT OPERATE TO PROVIDE GOOD AIR DISTRIBUTION QUALITY WITH THIS SYSTEM IF FURNACE...

Page 7: ...TO AND OUT OF THE HOUSE FRESH AIR SUPPLY HOOD STALE AIR EXHAUST HOOD FLEXIBLE INSULATED DUCTING WITH A VAPOR BARRIER VENTILATOR EXHAUSTS FROM KITCHEN AND OR BATHROOMS OR OTHER CENTRAL LOCATIONS TO OUT...

Page 8: ...1 Read these instructions carefully Failure to follow these instructions could damage the product or cause a haz ardous condition 2 Check the ratings on the product to make sure the prod uct is suita...

Page 9: ...confirm the proper polarity use a voltmeter or test lamp to make sure there is no power after the switch when the door is open Check between that point and ground on the cabinet This process must be...

Page 10: ...MOTOR DETAILS DEFROST DETAILS 205 ONLY DEFROST DETAILS 150 ONLY FAN MOTOR DIRECT MOUNTED CAPACITOR R E D W H I T E BLACK GREEN YELLOW ORANGE WHITE T9 T6 C A P PCB PLUG IN PLUG IN CONNECTOR RED RED ORA...

Page 11: ...KOUT After installation is complete check to be sure system is working correctly On units with microprocessor control select ventilation speed by touching fan control pad on base module until desired...

Page 12: ...e exhaust and fresh air supply hoods are not blocked or restricted by leaves grass or snow In winter be sure snow does not block hoods and frost does not accumulate on wire mesh bird screen IMPORTANT...

Page 13: ...conden sationappears on windows Dehumidistat is set too high Set dehumidistat lower Undersized ventilator hot tub indoor pool etc Cover pools and hot tubs when not in use Lifestyle of occupants Avoid...

Page 14: ...entilator drain lines Ensure O ring on drain nozzle adjusted correctly Look for kinks in line Ventilator is not level Level ventilator Drain lines are obstructed Check water drain connections Ventilat...

Page 15: ...r Foam Prefilter 11 Circuit Board for Damper Motor 12 208514 208514 Drain Spout 13 208515 208515 Drain T Fitting 14 208516 208516 Duct Collar Red 15 208517 208517 Duct Collar Blue 16 H Channel 24 3 4...

Page 16: ...wo 10 209722 209722 Clip for Foam Prefilter 12 208514 208514 Drain Spout 13 208515 208515 Drain T Fitting 14 208516 208516 Duct Collar Red 15 208517 208517 Duct Collar Blue 16 32002113 001 32002113 00...

Page 17: ...cting Elbow 4 in plastic 3 208373 Diffuser 4 in diameter 4 208374 Diffuser 5 in diameter 5 208375 Diffuser 6 in diameter 6 208379 Installation Parts Kit 7 272813 Flow Measuring Station 6 in 8 208372 A...

Page 18: ...FRESH AIR VENTILATION SYSTEMS 68 0269 18 Fig 12 HR150 and HR200 shown with manual control exploded view of parts keyed to HR Parts List 3 M15511B 1 2 4 5 6 7 25 8 8 12 13 14 15 23 22 24 21 28 16 17 1...

Page 19: ...R150 200 FRESH AIR VENTILATION SYSTEMS 19 68 0269 Fig 13 ER150 and ER200 shown with manual control exploded view of ER Parts List 3 M11889A 1 2 4 5 6 7 25 8 8 12 13 14 15 23 22 24 21 28 16 17 18 19 20...

Page 20: ...om yourhome Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limit e 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 HR150 200 ER150...

Reviews: