3.9.2.2
AC Available
The AC available signal monitors phases B & C of the AC from the input side of circuit breaker CB1. The AC
available LED’s will be illuminated green provided that both EMO breaker CB2 is on and the AC voltage is
above 170 VAC.
WARNING: IF EMO BREAKER IS OFF, THERE WILL BE NO INDICATION
AC IS PRESENT WITHIN THE PDU. WHENEVER WORKING ON THE PDU
ALWAYS FOLLOW LOCK OUT TAG OUT PROCEDURES AND MEASURE
FOR VOLTAGES BEFORE PERFORMING ANY WORK.
3.9.2.3
Main Power On
The Main power on signal monitors phases B & C of the AC on the output side of circuit breaker CB1. The
Main power on LED will be illuminated green provided that both input breaker CB1 is on and the AC voltage
is above 170 VAC.
3.9.2.4
48V DC on
The 48V DC on signal monitors the 48V DC output. The 48V DC on LED will be illuminated green
whenever the 48V DC output voltage is above 44 VDC.
3.9.2.5
Power Supply LED’s
The interface PCB contains LED’s to show the status of the power supplies. When the 48V DC bus is
enabled, all installed power supplies should have their corresponding LED illuminated green. If a power supply
is not installed or failed, the corresponding LED will be off. All power supply LED’s will be off when the 48V
bus is inhibited (off). Refer to
for a view of the rectifier good LED’s.
3.9.3
Test Points
Test points are provided on the interface PCB as shown in
. There is one set of test points for the
24V EMO supply output and one set for the 48V DC output. The test points are protected against short
circuit by re-settable fuses. For all test points, red is positive and black is negative.
3.9.4
Thermostat
A normally closed thermostat is located on the interface PCB which will shut down the PDU due to extreme
temperatures. The thermostat is rated 45
°
C +/- 5
°
C and is installed in the positive leg of the 24V EMO power
to the EMO loop. If the temperature reaches the thermostat set-point, the thermostat will open and trip input
breaker CB1 resulting in the shut down the PDU. The thermostat will automatically reset after the temperature
has reached about 35 degrees C, but the PDU will remain off since the input breaker will need to be turned on.
T
he thermostat should re-set within 1 minute as long as the temperature is 4 degrees below the trip range (trip range
is 40C - 50C).
The PDU will not be able to be turned on until the thermostat has reset. As shown in
,
the thermostat is located on the interface PCB, behind the test points. To check if the thermostat is
open/closed, refer to section 2.1 (item 7) of the Service Manual.