83488001 Revision N
Connect the three lines of the input power to the L1, L2, L3 terminals and the earth ground to
the terminal marked with the ground symbol (
). No neutral connection is required for the
200-240VAC configuration. For models with the 380-440VAC input configuration (340-
460VAC) the neutral wire must be connected to terminal marked N. The power connections
are not phase rotation sensitive, so any phase can be connected to any of the AC inputs.
Figure 4 AC Input Terminal Block
If the power supply was purchased with the 400VAC input configuration, in
addition to the three phases, the neutral wire must be connected to terminal
marked N. Failure to connect the Neutral wire in a 400VAC unit may result in
damage to the supply.
AC INPUT VOLTAGE
MODE
RECCOMENDED AC INPUT CABLE
SIZE & RATING
200-240VAC
(180-264VAC), 50-60 Hz, 3
Cap Charging
9mm
2
/8 AWG, 600V
Continuous DC
9mm
2
/8 AWG, 600V
380-440VAC
(340-460VAC), 50-60 Hz, 3
Cap Charging
6mm
2
/10 AWG, 600V
Continuous DC
6mm
2
/10 AWG, 600V
Table 2 Recommended AC Input Cable
The AC input rating is marked on the rear terminal of the power supply. The rating is also
part of the unit’s model description shown in Table 1.
Summary of Contents for 802 Series
Page 2: ...PAGE LEFT INTENTIONALLY BLANK ...
Page 10: ...4 83488001 Revision N Notes ...
Page 34: ...28 83488001 Revision N Notes ...
Page 44: ...38 83488001 Revision N Notes ...
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......