6-9. Parallel Operation
For parallel operation, method (B) is possible
L oad
O utput
T erm inal
O utput
T erm inal
L oad
O utput
T erm inal
O utput
T erm inal
(B) T o use as B ack-up Pow er S upply
1. A djust the output voltage of each pow er supply to be the sam e .
2. Set pow er supply output voltage higher by the forw ard voltage
drop (V f) of diode.
Use within the specification for output voltage and output power.
(A) To increase the output current is not possible.
Power Supply
Power Supply
(*4) Please select a reverse current prevention diode with maximum
forward current rating more than output load current
V +
V +
V -
V -
(*4)
6-10. Isolation Test
Isolation resistance between Output and
is more than 100M
Ω
at 500VDC. For safety operation, voltage setting of DC isolation tester
must be done before the test. Ensure that the unit is fully discharged after the test.
6-11. Withstand Voltage Test
These products are designed to withstand 4.0kVAC between input and output, 2.0kVAC between input and
and 1.5kVAC between output
and
for 1 minute. When testing withstand voltage, set current limit of the withstand voltage test equipment to 20mA. The applied voltage
must be gradually increased from zero to the testing value and then gradually decreased for shut down. When timer is used, the power supply
may be damaged by high impulse voltage at timer switch on and off. Connect input and output as follows.
Input – Output (Dashed line): 4kVAC, 1 minute (20mA)
Input –
(Solid line) : 2kVAC,1 minute (20mA)
Output –
: 1.5kVAC 1 minute (20mA)