13/22
TDK-Lambda
CUS600M
INSTRUCTION MANUAL
6-15. Remote Sensing (S+, S- terminal)
This function compensates the voltage drop of wiring from output terminals to load terminals. Connect “S+” terminal to “+” terminal of load
and “S-” terminal to “-” terminal of load with sensing wires. The total line voltage drop (+ side line and - side line) shall be less than 0.5V.
For /ADJ sub-model, the output voltage at the “V+” “V-” terminals shall be within the specification of output voltage range. In case that
sensing lines are too long, it is necessary to put an electrolytic at the load terminals.
V+
V-
CN51
CN61
Load
+
-
+
Power
Supply
7. Mounting Directions
7-1. Output Derating according to the Mounting Direction
Recommended standard mounting direction is (A). Mounting direction (B)-(E) are also possible. Refer to the output derating below.
Load (%) of derating curve indicates output power.