14/22
TDK-Lambda
CUS600M
INSTRUCTION MANUAL
7-2. Output Derating
Make sure that the specified temperature range is maintained.
Convection cooling @ universal input
CONDITION A: Output Derating Curve for Main Output Channel only, Standby Supply must be Zero Load.
Output derating versus input voltage should be considered.
Please refer to the output derating versus input voltage curve 6-1 for detail.
MODEL: CUS600M-19/24/28/32/36/48
Ta (°C)
Mounting A
Mounting B C E
Mounting D
LOAD (%)
LOAD (%)
LOAD (%)
-20 - +35
100
100
90
40 100
93.3
81.4
50 83.3
80
64.3
60 66.7
60
47.1
70 50
40
30
MODEL: CUS600M-12
Ta (°C)
Mounting A
Mounting B C
Mounting D
Mounting E
LOAD (%)
LOAD (%)
LOAD (%)
LOAD (%)
-20 - +35
100
100
90
90
40 100 93.3 81.4
82.9
50 83.3 80 64.3
68.6
60 66.7 60 47.1
54.3
70 50 40 30
40