83-517-000 Rev.
A
73
8.3
ISOLATED PROGRAMMING & MONITORING CONNECTOR
Refer to Table 8-1 for a detailed description of the rear panel Isolated Programming & Monitoring connector. To
provide the lowest noise performance, it is recommended to use shielded-twisted pair wiring.
Refer to Figure 8-1 for a description of the Isolated Analog Programming & Monitoring connector.
Isolated Analog Programming Plug P/N
: MC1.5/8-ST-3.81, Phoenix.
Figure 8-1: Isolated Programming and Monitoring Connector
Terminal
Signal name
Function
Range
(IS510 option)
Range
(IS420 option)
1
SHLD
Shield, connected internally to
chassis of the supply.
Chassis ground
2
+VPROG_ISO
Output Voltage programming
input
0-5V/0-10V
4-20mA
3
+IPROG_ISO
Output Current programming
input
0-5V/0-10V
4-20mA
4
GND
Ground for programming
signals.
Ground
Ground
5
GND
Ground for programming
signals.
Ground
Ground
6
+VMON_ISO
Output voltage monitoring
output
0-5V/0-10V
4-20mA
7
+IMON_ISO
Output current monitoring
output
0-5V/0-10V
4-20mA
8
SHLD
Shield, connected internally to
chassis of the supply.
Chassis ground
Table 8-1: Description of Isolated programming & Monitoring Connector
CAUTION
When the Isolated Analog Option is installed,
DO NOT
apply any signals to the non-isolated
VPGM and IPGM (J1-9 and J1-10) pins. All other J1 features may be used normally. Refer to
Section 4.5 for a description of J1 features.
Parallel Operation
: The optional Isolated Analog (IS510/IS420) Interface must be installed in
both the
Master
and
Slave
unit.