background image

 

 

-10- 

TDK-Lambda 

HWS1000 Series

 

INSTRUCTION MANUAL

   

 

5. Functions and Precautions 

5-1. Input Voltage Range 

Input voltage range is single phase 85 

  265VAC (47 

  63Hz). Input voltage, which is out of specification, may 

cause unit damage. Rated input voltage range fix during safety standard application is from100V to 240VAC (50/60Hz). 

While applying input voltage from 85Vac to 90Vac, output load current derating is required. 

 

5-2. Output Voltage Range 

Output voltage is set to the rated value at shipping. V.ADJ trimmer on the front panel side is use to adjust the output 

voltage within the range specified. Output voltage trimming range is within -20% 

  +20% of the rated output voltage 

(48V, 60V model: -20% 

  +10%). Turn the trimmer clockwise to increase output voltage. Take note when the output 

voltage is increased excessively over voltage protection (OVP) function may trigger and output voltage will shut down. 

Use the output power of the power supply below the rated output power value when you raise the output voltage. 

 
5-3. Over Voltage Protection (OVP) 

The  OVP  function  (Inverter  shut  down  method,  manual  reset  type)  is  provided.  OVP  function  operates  within 

125-145%  of  the  rated  DC  output  voltage  value  (3-7V  model:  125-140%,  36V  model:  125-138%,  48V,  60V  model: 
115-125%), and the output will be shut down when OVP function triggers. When OVP function operates, the input power 
is cut off for a few minutes, and then power is re-input or remote ON/OFF control signal shall be input for recovery of 
the output. OVP value is fixed and can not be adjusted.

 

 
5-4. Over Current Protection (OCP) 

The OCP function (Constant current limiting, Time delay shutdown type) is provided. OCP function operates when the 

output current exceeds 105% of maximum DC output current specification and the over current or short circuit condition 
continues 5-second or more, the output will be shut down. When the OCP is triggered, the input power is cut off for a 
few minutes, and then power is re-input or remote ON/OFF control signal should be input for recovery of the output. The 
OCP setting is fixed and not to be adjusted externally. 
 

5-5. Over Temperature Protection (OTP) 

Over  temperature  protection  function  (manual  reset  type)  is  provided.  When  ambient  or  internal  temperature  rises 

abnormally, OTP will shut down the output. When OTP is triggered, input power is cut off and allow sufficient cooling to 
reset  the  OTP  function. Then  power  is  re-input  or  remote  ON/OFF  control  signal  should  be  input  for  recovery  of  the 
output.

 

 

5-6. Low Output Detection Circuit (PF) 

Low  output  voltage  detection  circuit  is  provided.  Power  Fail  signal  (PF  signal)  will  output  when  output  voltage 

decrease by either the drop or brown out of the input voltage or OCP, OVP and OTP function operation. PF signal will 
turn “High” level to indicate the abnormal status of the power supply when the output voltage decrease to 80% of the 
output voltage setting value. However, there is a possibility that PF signal may not output during parallel operation. The 
PF signal circuit is insulated from the power supply input and output circuit and it is an open collector. TOG terminal is 
ground for PF terminal. 

When the Built-in Fan Motor of this power supply unit stops, PF signal will turn to “H” and the output power will shut 

down. The Built-in Fan Motor is a component with lifetime. We recommend a periodic replacement. Please contact our 
sales office. Replacement is at customer’s expenses. 
 
 
 
 
 
 
 
 
 
 
 
 

PF

 

TOG 

Vce max

30V 

Ic max

20mA 

Summary of Contents for HWS1000 Series

Page 1: ...changed or dis assembled Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc Please stop using it immediately and shut off the product It might le...

Page 2: ...ity of product failure or malfunction Provide countermeasure for prevention of lightning surge voltage as there is risk of damage due to abnormal voltage Connect together the frame ground terminal of...

Page 3: ...anical stress applied directly to the product Please keep away from direct sunlight For long term storage temperature and humidity the following conditions shall be used as a guideline Temperature ran...

Page 4: ...or use the shielded wire Remote ON OFF control lines shall be twisted or use the shielded wire 2 1 Front Panel Explanation HWS1000 Front Panel Output terminal Output terminal ON Output Power On indic...

Page 5: ...sensing function is unnecessary 5 PC Current balance terminal For output current balancing in parallel operation 6 COM Ground for PC and PV signal 7 PV Output voltage external control terminal For po...

Page 6: ...deteriorate when the sensing terminals are opened In the following cases the output is shut down When CNT and TOG is opened When PV and REF is opened Attached connector when shipping Connecting circu...

Page 7: ...ached to the product Connector JST S12B PHDSS Remove standard attached connector and use the harness made by the customer Housing JST PHDR 12VS Contact JST SPHD 001T P0 5 1 2 3 4 7 8 should be shorted...

Page 8: ...t 85 265VAC FG Output CNT TOG Remote ON OFF Control S S COM PV Output Current Balance PC PF Standby supply Latch Circuit OVP Circuit UVP Circuit Low output Voltage Detection Photo coupler Delay Circui...

Page 9: ...OFF REMOTE OFF REMOTE OFF REMOTE ON REMOTE ON REMOTE ON REMOTE ON FAN STOP FAN ALM ACTION OCP SHUT DOWN 5sec TYP 5sec TYP OCP Point 105 or more 3 OCP Shut down 1 Level 2 4V H 12V or Open 0V L 0 8V or...

Page 10: ...wn type is provided OCP function operates when the output current exceeds 105 of maximum DC output current specification and the over current or short circuit condition continues 5 second or more the...

Page 11: ...t is connected The output is turned to ON when TOG and CNT terminals are shorted and output is turned to OFF when these terminals are opened When the function is not used connect TOG and CNT terminals...

Page 12: ...pe is too long 5 10 Series Operation For series operation either method A or B is possible There might be a step in the rise waveform during series operation Note1 Please connect a diode for by pass w...

Page 13: ...r supply to be same value within 1 or 100mV whichever is smaller 2 Use same length and type of wires for all load lines 3 Maximum value of output current in parallel is up to 80 of all paralleled mode...

Page 14: ...Output CNT PF 100mA The applied voltage must be gradually increased from zero to testing value and then gradually decreased for shut down When timer is used the power supply may be damaged by high im...

Page 15: ...re will be no output Please consider the following characteristics below when operating the unit Connection Method Output Voltage Linearity Output FG chassis 500VAC 1min 300mA Output CNT PF 100VAC 1mi...

Page 16: ...use the output voltage within 20 120 of rated output voltage value 3V model 30 120 48V 60V model 20 110 Wires for control lines must be twisted wire or shield wire In addition maximum variable voltage...

Page 17: ...own low output detection function PF triggers the PF signal and set it to H and also output LED is switch off Under voltage lock out protection mode switch off input for a few minutes and then switch...

Page 18: ...cut off for a few minutes and then power is re input or remote ON OFF control signal should be input for recovery of the output Input voltage range AC180V 265V Continuous Peak output time Within 10 se...

Page 19: ...ase note that ventilation will be worsened in a dusty environment 4 Built in fan is limited life part which require periodic replacement Replacement will be charge 5 The ambient temperature of this po...

Page 20: ...or safety purposes connect protective earthing terminal to the mounting set ground terminal 6 Recommended torque for the terminal piece 7 Recommended wiring Recommended circuit protector AC250V20A Rec...

Page 21: ...minal connection is properly tighten by a regulated tightening torque 4 Check if the wire material is not too thin 5 Check if the output voltage control V ADJ is properly adjusted OVP might be trigger...

Page 22: ...iance with the Low Voltage Directive EMC Directive and RoHS Directive UKCA MARKING UKCA Marking when applied to a product or packing material for a product covered by this handbook indicates complianc...

Reviews: