background image

 

 

 

28 

 

83550001 Revision C 

 

7.2. 

Isolated Analog Programming (INA option) 

The INA option features galvanically isolated analog voltage/current programming/readback, 
and digital control/readback connections. Signals are isolated using fiber optics. The 
Accuracy, Linearity, Temperature coefficient and Stability specifications are limited to 
±0.01% when programming via the isolated analog interface. If the unit is equipped with 
floating return, the isolated analog interface should be specified. 

The interface pin connections are similar to the ANA interface except the front panel 
potentiometer wipers (pins 4 and 5) are not connected. Details are shown in Table 6 below. 

 

Pin 

Signal 
Name 

I/O 

Description 

CC LED 

+15V through 10k

 when unit is operating in Constant Current mode 

CV LED 

+15V through 10k

 when unit is operating in Constant Voltage mode 

I-MON 

Analog output current monitor signal, scaled 0-10V=0-100% rated 
current. Series  resistance is 11k

 

N/C 

 

Not connected 

N/C 

 

Not connected 

Digital 
Ground 

 

Ground for digital circuits, Isolated from chassis to 2,000V 

POL-SET 

Polarity set signal for units equipped with optional electronic polarity 
reversal. Open=positive polarity, connected to digital ground=negative 
polarity. 

V-SET 

Output voltage set point, scaled 0-10V=0-100% rated voltage. 
Resistance to ground approx. 10M



 

Analog 
Ground 

 

Analog ground, Isolated from chassis to 2,000V 

10 

+10V 

+10V reference, 2mA max. 

11 

V-MON 

Analog output voltage monitor signal, scaled 0-10V=0-100% rated 
voltage. Series  resistance is 11k

 

12 

HV ON 

Open=HV OFF, Connect to digital ground=HV ON 

13 

POL-
Status 

Output Polarity indicator for units equipped with optional electronic 
polarity reversal. +12V=Positive, 0V=Negative. 

14 

N/C 

 

Not connected 

15 

I-SET 

Output current set point, scaled 0-10V=0-100% rated current. 
Resistance to ground approx. 10M



 

Table 6. Isolated Analog Interface Signals (INA option) 

Remote operation via the INA interface is the same as the ANA interface. Note that the 
control modes described in sections 7.1.2 through 7.1.4 cannot be used. 

Summary of Contents for PHV Series

Page 1: ...OPERATOR MANUAL FOR PHV Series High Voltage POWER SUPPLY Document 83550001 Rev C TDK LAMBDA AMERICAS 405 Essex Road Neptune NJ 07753 Tel 732 922 9300 Fax 732 922 9334 Web www us tdk lambda com hp...

Page 2: ...ETHAL VOLTAGES PRESENT All power supplies contain hazardous voltage and energy The power supply must only be operated by qualified personnel who have read this operator s manual and are familiar with...

Page 3: ...ive 93 68 EEC European Community Conformity Assessment Product Mark IEC 348 Attention consult Accompanying documents IEC 60417 1 5036 Dangerous voltage IEC 60417 1 5019 Protective earth e g power line...

Page 4: ...necting the High Voltage Output 14 4 6 1 HV Output Polarity 14 4 6 2 Floating Output 14 4 6 3 HV Output Connector 14 5 CONTROLS INDICATORS CONNECTORS 16 5 1 Front Panel Layout 16 5 1 1 Overtemp LED Re...

Page 5: ...sired output voltage current levels 24 6 6 Turning ON the output 24 6 7 CC CV Mode Indication 25 6 8 Turning the unit OFF 25 7 ANALOG REMOTE CONTROL OPERATION 26 7 1 The Non Isolated Analog Interface...

Page 6: ...HV Half Rack Rear Panel with Reversible Output 21 List of Tables Table 1 PHV Model Description Format 7 Table 2 PHV HV Output Connector Types 15 Table 3 Front Panel Controls and Indicator Functions in...

Page 7: ...N ARE CONTAINED IN ADDENDA AND TAKE PRECEDENCE IF CONFLICTS EXIST PLEASE TAKE CARE TO REFER TO THE CORRECT INFORMATION FOR YOUR UNIT 1 2 Introduction TDK Lambda PHV series are state of the art precisi...

Page 8: ...or Correction reduces RMS current draw 1 3 2 Benefits Lightweight switchmode design Benchtop chassis configuration with optional rack mount kit Low output stored energy provides greater safety Immunit...

Page 9: ...n in a clean dry environment 1 5 2 This product is designed for pollution degree 1 1 5 3 This product is designed for Transient Overvoltage Category II 1 5 4 Ensure all covers are in place and securel...

Page 10: ...upply family For additional options the customer may contact the Sales Department at TDK Lambda Americas Special options are typically shown as a four digit suffix to the model number PHV 20 N 15 USB...

Page 11: ...8 83550001 Revision C 2 SPECIFICATION...

Page 12: ...9 83550001 Revision C Mechanical Details...

Page 13: ...ed Service Center should be contacted if The power supply is mechanically or electrically damaged The power supply requires on site calibration or replacement warning decals The customer has questions...

Page 14: ...11 83550001 Revision C This Page Left Intentionally Blank...

Page 15: ...may require addition of a system heat exchanger Do not operate bench top units without the feet installed Do not expose the unit directly to sunlight to avoid unwanted thermal effects 4 3 Orientation...

Page 16: ...e switch or circuit breaker must be located close to the power supply and within easy access of the operator The switch or circuit breaker must be marked as a disconnecting device for the equipment If...

Page 17: ...this connection should not be removed If required the Ground link can be removed and the HV return must be connected to Ground at the load In the event of load arcs or flashovers the return connector...

Page 18: ...nstalled on one end PHV100PXX S1100 2 DS 2124 4 9ft cable with connector installed on one end PHV150PXX S1155 2 DS 2121 4 9ft cable with connector installed on one end PHV200PXX PHV300PXX Call factory...

Page 19: ...ode switch 1 and power on switch The PHV can be operated locally from the front panel or remotely 1 via an optional remote interface located on the rear panel Typical front panel layout of the PHV pow...

Page 20: ...utput is turned ON 5 1 13 14 HV ON OFF Button Turns HV Output ON OFF does not disconnect the HV output or AC Input 5 1 14 15 NEG Polarity LED 1 If optional polarity reversal is installed Illuminates t...

Page 21: ...approximately 0 1 to 100 of rated This control will only operate in local mode if the supply is operated in remote mode the local voltage set control has no effect 5 1 6 OVP Indicator LED Ref 6 Indica...

Page 22: ...lly hazardous voltage may be present 5 1 14 HV ON OFF Button Ref 14 DO NOT DEPRESS THE HV ON PUSH BUTTON UNLESS A SUITABLE LOAD IS CONNECTED TO THE POWER SUPPLY S OUTPUT CABLE AND THE LOAD IS CORRECTL...

Page 23: ...both remote analog and digital interfaces is operating in remote control mode via the Digital interface 5 1 23 Busy LED Ref 23 Indicates presence of traffic on the optional Digital interface 5 2 Rear...

Page 24: ...ce connector 5 2 3 4 Remote Interface 15pin sub D type receptacle for remote analog control interface 5 2 4 5 GND stud M4 for 1 AC inputs M6 for 3 AC inputs 5 2 5 6 Fuse AC power fuse 5 2 6 7 AC Input...

Page 25: ...al Interface Ref 3 Location of optional Digital control interface Options are USB IEEE 488 LAN Ethernet RS232 RS422 RS485 Profibus 5 2 4 Remote Analog Connector Ref 4 A 15 pin D sub female connector t...

Page 26: ...23 83550001 Revision C This Page Left Intentionally Blank...

Page 27: ...the limit voltage is displayed on the VOLTAGE meter To operate with no output voltage limit turn the V LIMIT potentiometer fully clockwise The V LIMIT LED will extinguish Once the OVP limit has been s...

Page 28: ...gure 1 The ON LED will extinguish Item 12 in Figure 1 to show the HV output is OFF Wait until the output voltage has reached a safe potential then turn off the POWER switch Item 11 in Figure 1 This pr...

Page 29: ...rface INA option features up to 2kV isolation from chassis ground 7 1 The Non Isolated Analog Interface ANA option Note that analog and digital ground pins 6 and 9 for the external programming signals...

Page 30: ...els set by 0 10V signals and HV ON OFF function by switches or relay contacts Some examples for operating the unit in various combinations of LOCAL and REMOTE modes are shown in sections 7 1 2 through...

Page 31: ...ies resistance is 11k 4 N C Not connected 5 N C Not connected 6 Digital Ground Ground for digital circuits Isolated from chassis to 2 000V 7 POL SET I Polarity set signal for units equipped with optio...

Page 32: ...29 83550001 Revision C This Page Left Intentionally Blank...

Page 33: ...rface supports up to 2000 programming commands per second To operate the unit in Remote Digital mode set the LOCAL REMOTE switch see Item 18 in Figure 2 to the REMOTE position the LOCAL LED will extin...

Page 34: ...31 83550001 Revision C This Page Left Intentionally Blank...

Page 35: ...channel and Master Pin 5 to Slave Pin 15 for the Current channel Hard wire Slave Pin 12 to Slave Pin 6 to turn on the HV output The HV output cables must be connected together at the load 9 2 Paralle...

Page 36: ...33 83550001 Revision C This Page Left Intentionally Blank...

Page 37: ...34 83550001 Revision C Notes...

Page 38: ...plication issues or questions that are not covered in this manual please do not hesitate to contact the factory and our team of experienced HV application engineers Contact the Factory We are here to...

Reviews: