408-3194

2

 of 3

Rev 

K

2. Flex the wings of the cable while removing the 

cable from the reel. 

3. From the distribution point (wall box or floor 

fitting), lay the cable on the floor with the printed 

side of the cable facing up and the bow of the cable 

pointing up. Refer to Figure 2, Detail A. 

If more than two cable runs exit the distribution 

point, remove the inner wing of each cable, then 

place the cables side by side. See Figure 2, 

Detail A.

To remove the inner wing, use Cable Notcher Tool 

1725698-1 (available separately) to cut a notch to 

the groove in the wing; then, flex the wing and tear 

it back slowly. DO NOT cut into the center rib 

containing the conductors. See Figure 2, Detail B.

4. Place hold-down tape over the cable area. See 

Figure 2, Detail A.

Hold-Down Tape 553481-1 is available separately.

5. Cross-tape as required along the cable run. 

Stretch the tape to remove any slack.

Spray Adhesive 553453-1 is available separately 

and may be used to aid in adhering the tape to the 

cable and floor surface.

6. If extra protection for the communications cable is 

desired, install Floor Preparation 554123-[ ] and Top 

Shield 553536-[ ] according to 408-3150; both are 

available separately.

The communications cable does not require a top 

shield or bottom shield; however, local inspection 

requirements and certain floor finishes are 

examples where extra protection for the cable 

would be desirable.

7. If the cable requires directional changes, proceed 

as follows:

a. Using Cable Notcher Tool 1725698-1, notch 

the wings of the cable at 25.4-mm [1.0-in.] 

intervals. Make sure to remove all notched 

material. Refer to Figure 3, Detail A.

DO NOT cut into the center rib of the cable 

containing the conductors.

b. Bend the cable to form a gradual turn. Refer 

to Figure 3, Detail B for recommended length 

and radius. Cover the turn with hold-down tape 

to blend the profile of the cable at the notches. 

DO NOT fold the cable. Cable must be notched and 

cable bends must be gradual.

Figure 2

8. Terminate the cable to the transition block and 

floor fitting outlet according to the instructions 

included with the product.

NOTE

i

NOTE

i

NOTE

i

NOTE

i

!

CAUTION

!

CAUTION

Printed Side 

of Cable

Bow of Cable

Floor

Detail B

Notch in Wall 

Hold-Down 

Tape (Ref) 

Over Cable

Distribution 

Point

1 or 2 Cable Runs

More Than 2 Cable Runs

Hold-Down 

Tape (Ref) 

Over Cable

7.92 mm [.312 in.] 

(Typ) Centerline 

to Centerline 

of Cable

Detail A

Inner Wing 

of Cable

Cut Notch

Tear Back

Groove

Inner Wing of 

Cable Removed 

(See Detail B)

Cable

Orienting Communications Cable

Laying Communications Cable