Energy 2510 B
Vers. 001
GB
18
Fuel is fed to the internal combustion engine via
a pump fitted to the generating set as part of the
standard supply.
5.1 Machine
safety
The generating sets come with perfectly sealed
casings, so there is no danger of contact with any
moving or high temperature parts or with live
cables.
The doors open with a lock and key. The keys
must not be left within the reach of children or
inexperienced persons.
The generating sets
must only and exclusively be used with their
doors shut.
Remove any flammable substance (for
example: petrol, paints, solvents, etc.) from
near the generating sets.
Make sure that any hot parts of the
generating sets are not in contact with any
flammable material.
Never fill up the fuel tank while the engine is
running.
Never touch the generating sets or the wiring
connections with wet hands.
Never replace the fuses or the cut-out
switches with others having higher
amperage.
Should any electrical part need checking, this
must only be done with the engine turned off
and by specialised personnel.
The generating sets have been built in
compliance with the safety standards listed in the
EEC statement of compliance.
6 USING THE GENERATING SET
6.1 Starting up the generating set
The generating sets are provided with an
electronic remote control panel which allows you
to perform starting up / turning off operations and
to check their running conditions.
The panel controls are:
1 ON/OFF
switch
2 Display
unit
3 High temperature indicator
4 Engine minimum oil level indicator
5 Startup failed
6 Generator running (flashing)
7 Engine oil change indicator
8 Fuel warning light
9 Display time changeover switch
10 Reset
Set the startup switch (Fig.30 Ref.1) to its “
ON
”
position. The message “WAIT” will be displayed
for 8 seconds. After this time, the electronic
control panel will start the first automatic
procedure for starting up the generating set. If
the engine starts up at the end of this phase, the
“generator running” indicator light (Fig.30 Ref.6)
will start to flash.
Should the engine not start up, this automatic
procedure will be repeated up to 4 times.
If, at the end of a complete cycle, the engine has
not yet started up, the “startup failed” indicator
(Fig.30 Ref.5) will light up to signify that the
generating set has failed to start up.
If the “startup failed” indicator (Fig.30 Ref.5) light
only stays lit, you can repeat the procedure
several times.
If the generating set has not started up after
several attempts, contact the manufacturer’s
After-sales service.
Should the battery be flat, you can start the
generating set by hand, using the handle of the
engine coil winding (Fig.31 Ref.1) after setting
the selector switch to "ON" (Fig.31 Ref. 2) and
the electronic control panel to "ON".
Once you have started up the engine manually,
put the selector switch back to "0FF" (Fig.31 Ref.
2). The start-up battery should never be
disconnected, as there would be no input to the
electronic control panel which would prevent the
generating set from working.