20
3.7 Installation of UPS with AC inputs
CAUTION:
Online 6K/10K series support that the UPS can have
separate AC inputs. So before connecting wires of seperate AC
inputs, you should confirm that their earthing systems are identical.
Otherwise, a transformer is necessary.
UPS with common Normal and Bypass AC inputs
UPS with separate Normal and Bypass AC inputs
Ø
Earthing systems are identical:
Ø
Earthing systems are separate:
Three different installations can be choosen:
1)
Transformer in the Normal AC input.
21
2)
Transformer in the Bypass AC input.
3)
Both of them have transformer
Frequency converter (without Bypass AC input)
Summary of Contents for AP160N-6K