42
Figure. 5-15 Event menu tree
5.4.4 The measurement menu
By pressing
on the menu of “Measurement”, the display would
enter the next measurement menu tree.
A lot of detailed useful information could be checked here, Ex. the
output voltage and frequency, the output current, the load capacity,
the input voltage and frequency, etc.
By pressing
>1s, the display would return the last main menu
tree.
43
Figure. 5-16 Measurement menu tree
5.4.5 The control menu
By pressing
on the menu of “Control”, the display would enter
the next control menu tree.
1) Start Battery Test: this is one command that control the UPS to
do the battery test.
2) Clear EPO status: once EPO status is enabled, the UPS output
would be cut off. To recover to normal status, first EPO
connector should be closed, and enter this menu to clear EPO
status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
3) Reset Fault status: when fault occurs, UPS would keep in Fault
mode and alarm. To recover to normal status, enter this menu
Summary of Contents for AP160N-6K