52
Current
26.4A@230Vac
44.0A@230Vac
Power Factor
≥
0,99 @100% Nominal Load
≥
0,98 @50% Nominal Load
≥
0,95 @25% Nominal Load
THDI
< 5 %@Full load and battery full charged
Battery & Charger
Battery
180VDC / 5Ah
240VDC / 9Ah
Current
39A
48A
Charger current
1A
1.7A
7.2 Dimension and Weight
Dimension
(W*D*H) mm
438*698*129
438*704*215.5
Net Weight (KG)
46
82.5
Gross Weight (KG)
50
87.5
7.3 Operating Environment
Item
6K/10K
Standards/Comments
Cooling
Force Air Cooling
/
Operating
Temperature
Range
0°C ~ 40 °C
Nominal power & continuous
operating mode
-15°C~60°C
UPS
Storage
Temperature
0~35°C
Battery
Relative
Humidity
0-95%
No condensing
Altitude
<1000m for Nominal power
Over 1000 m the power
derating is 1 % every 100 m
Acoustic
Noise
<55dB
/
53
8. Troubleshooting
The online series UPS is designed for durable, automatic operation
and issues alarms to alert you whenever potential operating
problems occur. Usually the alarms shown by the control panel do
not mean that the output power is affected. Instead, they are
preventive alarms intended to alert the user. Active alarms are
accompanied by an audible buzzer.
The control panel provides troubleshooting information from two
main menus:
l
UPS status menu: Access to all active alarms
l
Event Log menu: Access to the most recent 50 events, which
may include active and closed alarms
8.1 Typical Alarms and Conditions
Alarm or Condition
Possible cause
Action
ON Maintenance
Bypass
Alarm Code: 72
UPS was manually
commanded to switch to
bypass and will remain in
bypass until commanded
out of bypass
Check the maintain bypass
switch status
In Battery Mode
Alarm Code: 62
A utility failure has
occurred and the UPS is
in Battery mode.
The UPS is powering the
equipment with battery
power. Prepare your
equipment for shutdown.
In ECO Mode
Alarm Code: 63
The UPS is on bypass
while operating on the
High Efficiency setting.
The equipment transferred
to bypass utility power as a
normal function of High
Efficiency operation. Battery
mode is available and your
equipment is protected.
EPO Active
Alarm Code: 71
The external contacts in
the rear of the UPS are
configured for REPO
operation and they have
been activated.
Check the EPO connector
status