2. Safety Warnings 

 
 
 
 
 
 
 

IMPORTANT  SAFETY  INSTRUCTIONS  FOR  EACH  STEP  SAVE 

THESE INSTRUCTIONS. 

2.1 Installation 

l

 

Condensation  may  occur  if  the  UPS  is  moved  directly  from  a 

cold to a warm environment. The UPS must be absolutely dry 

before being installed. Please allow an acclimatization time of 

at least two hours. 

l

 

Do not install the UPS near water or in damp environment. 

l

 

Do  not  install  the  UPS  where  it  would  be  exposed  to  direct 

sunlight or near heat. 

l

 

Do not block ventilation openings in the UPS’s housing. 

l

 

Place cables in such a way that no one can step on or trip over 

them. 

l

 

UPS has provided earthed terminal, in the final installed system 

configuration,  equipotent  earth  bonding  to  the  external  UPS 

battery cabinets. 

l

 

An integral single emergency switching device which prevents 

further  supply  to  the  load  by  the  UPS  in  any  operation  mode 

should be provided in the building wiring installation. 

l

 

An  appropriate  disconnect  device  as  short-circuit  backup 

protection should be provided in the building wiring installation. 

l

 

For  the  equipment  connection  to  an  IT  power  system,  a 

two-pole  device  which  disconnect  phase  conductors  and  the 

CAUTION:

   

Before performing the procedures in this document, read and follow 

the  safety  instructions  and  important  regulatory  information  in  your 

Safety, Environmental, and Regulatory Information document. 

neutral  conductor  have  to  be  provided  in  the  building  wiring 

installation. 

l

 

This is permanently connected equipment , it must be installed 

by qualified maintenance personnel. 

l

 

For  permanently  connected  equipment: 

make  sure  that  a 

readily  accessible  disconnect  device  is  incorporated  in  the 

building installation wiring. 

        To reduce the risk of fire, connect only to a circuit provided with 

branch  circuit  overcurrent  protection  with  an  ampere  rating  in 

accordance  with  the  IEC/EN  60934  standard  or  your  local 

electrical code and have a contact air gap of at least 3 mm. 

Uninterruptible power supply 

output power 

240V 

6K 

40 amp 

2-pole circuit breaker 

10K 

63 amp 

2-pole circuit breaker 

l

 

You  can  connect  four  extended  battery  modules  to  the 

uninterruptible power supply.

   

l

 

Earthing  connection  is  essential  before  connecting  to  the 

building wiring terminal.   

2.2 Operation 

l

 

Do not disconnect the earth conductor cable from the UPS or 

the building wiring terminals in any time since this would cancel 

the  protective  earthing  of  the  UPS  system  and  all  connected 

loads. 

l

 

The UPS output terminal block may be electrically active even if 

the  UPS  system  is  not  connected  to  the  building  wiring 

terminal. 

l

 

In  order  to  completely  disconnect  the  UPS,  firstly  press  the 

OFF button, and then disconnect the mains lead. 

Summary of Contents for AP160N-6K

Page 1: ...tup 19 3 7 Installation of UPS with AC inputs 20 4 Power cables connection Startup 22 4 1 Access to terminal block 23 4 2 Common input sources connection 23 4 3 Separate input sources connection 24 4...

Page 2: ...wer problems such as power failures power sags power surges brownout and line noise Power outages can occur when you least expect them and power quality can be erratic These power problems have the po...

Page 3: ...timize recharge time l Selectable High Efficiency mode Eco Mode of operation l Start on battery capability for powering up the UPS even if utility power is not available l Standard communication optio...

Page 4: ...fety instructions and important regulatory information in your Safety Environmental and Regulatory Information document 5 neutral conductor have to be provided in the building wiring installation l Th...

Page 5: ...high short circuit current and pose a risk of shock Take all precautionary measures specified as below and any other measures necessary when working with batteries 1 Remove all jewellery wristwatches...

Page 6: ...ns and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage Note Check the battery rech...

Page 7: ...on on each side carefully lift the cabinet out of the outer carton using the handles on the cardboard and set it on a flat stable surface see Figure 3 3 3 4 Place the cabinet in a protected area that...

Page 8: ...it for future use 3 3 UPS Rear Panel This section shows the rear panel of the Online R T models 6K model Figure 3 5A 6K Rear Panel single parallel without maintenance bypass 13 Figure 3 5B 6K PDU Rea...

Page 9: ...binets into the rack requires a minimum of two people CAUTION Removing the batteries requiered precautions which should be performed or supervised by personnel with knowledge of batteries Keep unautho...

Page 10: ...g rails in the rack then install the UPS in the sliding rail 17 Figure 3 12 Install the sliding rails 7 For 10K Install the battery pack and battery protection plate then fix the front panel Figure 3...

Page 11: ...2 Replace UPS s front panel and EBM s front panel Figure 3 15 Replace UPS s front panel and EBM s front panel 19 10K Model Figure 3 16 Plug the EBM cable into the UPS battery connector 3 6 Tower Setu...

Page 12: ...systems are identical Otherwise a transformer is necessary UPS with common Normal and Bypass AC inputs UPS with separate Normal and Bypass AC inputs Earthing systems are identical Earthing systems are...

Page 13: ...ery Cabinet Positive Pole Negative pole Min conductor cross section 4mm 2 10AWG 10mm2 6AWG External Battery Cabinet Fuse in Positive Pole Negative pole 60A 80A The UPS does not have an automatic prote...

Page 14: ...do not exceed the UPS capacity to prevent an overload alarm 1 Verify that the internal batterties are connected 2 If optional EBMs are installed verify that the EBMs are connected to the UPS 3 Set th...

Page 15: ...on the UPS display Deactivate the external REPO switch and restart the UPS 4 6 Parallel Installation and Operation 4 6 1 Brief introduction of the redundancy The parallel structure is 1 1 As long as...

Page 16: ...28 Figure 4 5 a Parallel systerm wiring diagram of 6K 10K 29 Figure 4 5 b Parallel System Installation Diagram...

Page 17: ...press the button to turn off the UPS then UPS will work in bypass mode 31 4 Set the main maintenance bypass switch from UPS to ByPass then switch off the main output breaker and the input breaker and...

Page 18: ...in menu Press this button for 1s to exit the present menu to default system status display menu without executing a command or changing a setting Scroll up Press this button for 0 1sec 1s to scroll up...

Page 19: ...operating mode or status 35 Table 5 3 Status Summary Screens Status Summary Screen Description Fig 5 3 Normal mode The UPS is operating in Normal mode from utility power Fig 5 4 Battery mode When the...

Page 20: ...bypass and keep alarming The backlight of LCD would also turn to red 37 Fig 5 11 Overload When the UPS is overload the alarm will beep twice every second Some unnecessary loads should be get rid of on...

Page 21: ...order to cut off the UPS output simply cut off the utility power supply A few seconds later LCD display shuts down and no output voltage is available from the UPS output terminal 5 3 4 Turning off UP...

Page 22: ...atus please see Fig5 14 5 4 3 The event log menu By pressing on the menu of Event log the display would enter the next event menu tree All the previous events alarm and fault have been recorded here T...

Page 23: ...menu tree 5 4 5 The control menu By pressing on the menu of Control the display would enter the next control menu tree 1 Start Battery Test this is one command that control the UPS to do the battery...

Page 24: ...press on the menu of Identification the display would enter the next identification menu tree The identification information includes UPS serial number firmware serial number model type would be show...

Page 25: ...unction loss even directly damage the load battery or UPS Most of settings could only be done while UPS is in Bypass mode Figure 5 19 Setting menu tree 47 Example set rated output voltage value Figure...

Page 26: ...disconnected from utility power 2 Place the UPS on a flat stable surface with the front of the cabinet facing you 49 3 Remove the UPS front cover 4 Disconnect the internal battery connectors 5 Fix the...

Page 27: ...chapter provides the following specifications l Model list l General Specification l Electrical Performance l Environmental and Safety 7 1 Electrical specification Model Online RT 6K Online RT 10K Ou...

Page 28: ...y are preventive alarms intended to alert the user Active alarms are accompanied by an audible buzzer The control panel provides troubleshooting information from two main menus l UPS status menu Acces...

Page 29: ...s replaced Contact your service representative 55 Output Overload Alarm Code 41 Output is overload Remove some of the equipment from the UPS The UPS continues to operate but may switch to Bypass mode...

Page 30: ...e charger until the next power recycle Contact your service representative Battery Over Voltage Alarm Code 16 Indicates that the battery voltage is too high The UPS will turn off the charger until the...

Page 31: ...itiates the saving of all data and an orderly shutdown of the equipment The cable pins for the RS 232 communication port are identified in figure 9 1 and the pin functions are described in Table 3 Fig...

Page 32: ...your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this software users can monitor and control any UPS on the same LAN no matter how far fr...

Page 33: ...62 614 08108 00...

Reviews: