background image

 

30 

8. Trouble Shooting 

If the UPS system does not operate correctly,  check the  operating status  on the LCD 

display. 

Warning 

String   

Fault 

String 

Site fail 

SITE 

Inverter short 

SHOR 

Fan fail 

FANF 

Overload fault 

OVLD 

Battery over voltage (over charged) 

HIGH 

Inverter soft start fail 

ISFT 

Battery low 

bLOW 

Bus soft start fail 

bSFT 

Charge fail 

CHGF 

Over temperature fault 

OVTP 

Inverter temperature high 

TEPH 

Inverter Volt Low 

INVL 

Ambient temperature high 

AMbH 

Inverter Volt High 

INVH 

Battery open 

bOPN 

Bus volt over 

bUSH 

Overload   

OVLD 

Bus volt Low 

bUSL 

EPO 

EPO 

Bus Unbalance 

bUSE 

 

 

Inverter NTC open 

NTCO 

If  the  UPS  system  does  not  operate  correctly,  please  attempt  to  solve  the  problem 

using the table below. 

Problem 

Pzle cause 

Remedy 

No indication, no warning 
tone even though system 
is connected to mains 
power supply 

No input voltage 

Check building wiring socket outlet 
and input cable. 

Display Mode 
string ”STbY” in LCD, 
even though the power 
supply is available 

Inverter not switched on 

Press On-Switch “I”. 

Display Mode 
string ”bATT” in LCD, and 
audible alarm sounding 
every 1 beep in every 4 
seconds 

Mains power supply has 
failed, or Input power and/or 
frequency are out of tolerance 

Switching to battery mode 
automatically.   
Check input power source and inform 
dealer if necessary. 

Emergency supply period 
shorter than nominal value 

Batteries not fully charged / 
batteries defect 

Charge the batteries for at least   
5 - 8 hours and then check capacity. 
If the problem still persists, consult 
your dealer. 

Fan fail 

Fan abnormal   

Check if the fan is running 

Battery over voltage 

Battery is over charged 

Stop charging to battery 

automatically, and after the battery 
voltage is normal and the mains is 
normal, charge automatically again. 

Battery low 

Battery voltage is low 

When audible alarm sounding every 

second, battery is almost empty. 

 

31 

Charge fail 

The charge is broken 

Notify dealer. 

Inverter temperature high 

Inside temperature of the UPS 
is too high 

Check the ventilation of the UPS, 
check the ambient temperature. 

Ambient temperature high 

The ambient temperature is 
too high 

Check the environment ventilation. 

Battery open 

Battery pack is not connected 
correctly 

Check the battery bank is connected 
to the UPS. 
Check the battery breaker is turn on. 

Overload   

Overload 

Check the loads and remove some 
non-critical loads.   
Check whether some loads are 
failed. 

Site fail 

Phase and neutral conductor 
at input of UPS system are 
reversed 

Rotate mains power socket by 180° 
or connect UPS system. 

EPO active 

EPO function is enabled 

Turn off the EPO switch. 

Bus fault(Low/high/ 
Unbalance/soft start) 

UPS internal fault 

Notify dealer 

Inverter 
fault(Low/high/soft start) 

UPS internal fault 

Notify dealer 

Over temperature fault 

Over temperature 

Check the ventilation of the UPS, 
check the ambient temperature and 
ventilation. 

Inverter short 

Output short circuit 

Remove all the loads. Turn off the 

UPS. Check whether the output of 
UPS and loads is short circuit. Make 
sure the short circuit is removed, and 
the UPS has no internal faults before 
turning on again. 

Please  have  the  following  information  at  hand  before  calling  the  After-Sales 

Service Department: 

1.  Model number, serial number 
2.  Date on which the problem occurred 
3.  LCD display status, Buzzer alarm status 
4.  Utility  power  condition,  load  type  and  capacity,  environment  temperature, 

ventilation condition 

5.  The information (battery capacity, quantity) of external battery pack if the UPS 

is “S” model 

6.  Other information for complete description of the problem 
 
 
 
 

 
 
 

Summary of Contents for AP160N Series 1000VA

Page 1: ...iption 17 5 Connection and Operation 19 5 1 Inspection 19 5 2 Connection 19 5 3 Battery charge 21 5 4 Turn on the UPS 21 5 5 Test function 21 5 6 Turn off the UPS 22 5 7 Audible alarm mute function 22...

Page 2: ...ssure to connect with the earth reliably Assure external battery source must be earthed Connect the UPS only to an earthed shockproof socket outlet The building wiring socket outlet shockproof socket...

Page 3: ...the end of the tower 2 Place down the UPS into two stands carefully 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel 5 l Rack mount...

Page 4: ...battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reas...

Page 5: ...the gate and then reassemble front panel B C A D E 9 Note Three or more EBMs can be connected to the UPS in the same way as shown above Note After connect the EBMs please do not forget to set the num...

Page 6: ...alified maintenance personnel 1 3 1 UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the s...

Page 7: ...ake on off the load To test batteries 1 Connect the UPS to utility power for at least 48 hours to charge the batteries 2 Press and hold the I button 1 second to start the battery test on line mode or...

Page 8: ...D IEC EN 61000 4 2 Level 3 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips IEC EN 61000 4 1...

Page 9: ...KS Extended backup time 17 4 Panel Description The Display Panel Switch Function ON Button Turn on UPS system By pressing the ON Button I the UPS system is turned on Deactivate acoustic alarm By press...

Page 10: ...orm the transport agency immediately should you find signs of damage Please keep the packaging in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to pre...

Page 11: ...ed 5 4 Turn on the UPS 1 With utility power connecting Press I button continuously for more than 1 second to turn on the UPS the UPS will get into the inverter mode the LCD screen will indicate the st...

Page 12: ...will cause abnormality or permanent damage 2 One hard wiring type battery terminal on the rear panel is used for connecting the battery pack 3 The battery connection procedure is very important Any i...

Page 13: ...nominal power capacity 25 Note Please follow the following steps to connect the generator l Activate the generator and wait until the operation is stable before supplying power of the generator to th...

Page 14: ...hile the utility power is in normal range so the high efficiency could be gained in the ECO mode Once the mains is loss or abnormal the UPS would transfer to battery mode and the load is supplied cont...

Page 15: ...for more than 10 seconds the setting mode exit automatically The output frequency string OPF Bypass status string bYPA operating mode string MOdE Battery string bSTR Load segment string LS1 and LS2 wo...

Page 16: ...battery voltage is normal and the mains is normal charge automatically again Battery low Battery voltage is low When audible alarm sounding every second battery is almost empty 31 Charge fail The cha...

Page 17: ...d start the UPS If it needs to replace the batteries while the UPS is running make sure the UPS would not shut down during the replacement If there is a battery breaker then turn it off first Disconne...

Page 18: ...a computer connect one end of the serial communication cable that comes with the UPS to the RS 232 port on the UPS Connect the other end of the serial cable to the RS 232 port on a computer The cable...

Page 19: ...er WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems...

Page 20: ...1 AC Output 2 EPO Dry input Communication Port 3 USB Port 4 AC Input 5 Dry out 6 SNMP slot 7 RS232 8 Modem Network Surge Protection 9 Earth Line connection 39 1 1 3K Standard model rear panel 3K KS mo...

Reviews: