Ain modular UPS manual
- 19 -
Command data
Setting data1
Setting data2
Setting data3
Setting data3
Record data
Battery Test
Buzzer Set
Mute
Default Set
30KVA
22-12-2008
ID:01
08:30
◄
Setting
Record
Version
►
Language
Change Password
Date Setting
2008-12-22 08:30:00
Back-Light Delay
10Min
Contrast
20
Self-Test Date
STA 18:36
FOR:60min
Back
Timing of ON/OFF
ON:MON 08:48
OFF:SUN 17:25
Next
30KVA
22-12-2008
ID:01
08:30
◄
Setting
Record
Version
►
Work Mode
Single
LBS Group Setting
Master
System Voltage Level
220V
System Frequency Level
50HZ
Auto Turn-on
Enable
Bypass Frequency Range
2%
Bypass Volt. Upper Limit
10%
Back
Bypass Volt. Lower Limit
-30%
O/P Volt Micro tuning
0%
Next
30KVA
22-12-2008
ID:01
08:30
◄
Setting
Record
Version
►
Parallel ID
01
M/S hot standby Cyc.
Invalid
UPS Output
Enable
Pre-Alarm Time
14 Min
Float Volt Revise
0.001
Parallel Amount
04
Parallel Redundancy
01
Back
Next
30KVA
22-12-2008
ID:01
08:30
◄
Setting
Record
Version
►
Single Battery Volt.
12V
Battery Number
20
Battery Group
1
Single Battery Capa.
100AH
Boost Upper Limit Volt.
2.31
Float Base Volt.
2.25
Battery Protect Volt.
1.70
Boost Charge
Enable
Back
Boost Last Time
231 Min
Max Charge Current
25A
Next
30KVA
22-12-2008
ID:01
08:30
◄
Setting
Record
Version
►
0001
12-21 15:00:26
On Line
0002
12-21 15:00:25
Rectifier Active..
0003
12-21 15:00:10
Int.Input Switc..
0004
12-21 15:00:08
Int.Bypass Swit..
0005
12-21 15:00:05
Int.Output Swit..
0006
12-21 15:00:00
Ext. Output Swit..
Back
Next
30KVA
22-12-2008
ID:01
08:30
◄
Setting
Record
Version
►
SYS Version: V02
×
10
LCD Version: 701
×
02F
30KVA
22-12-2008
ID:01
08:30
◄
Setting
Record
Version
►
ID:00
Record:0001
▲
2008-12-21 15:00:25
Status:On Line
▼
Event: On Line
Alarm:
CODE:CC00-0000 DF00-0000
0000
0000-0000
0000-0000
Quit
ONLINE
Command
ONLINE
ONLINE
Command
Command
ONLINE
ONLINE
Command
Command
ONLINE
ONLINE
Command
Command
Tech Novitas FZC: P.O. Box 8073 Q3-144 SAIF ZONE, UAE Phone no.: +971 6 5529892
Tech Novitas (FAR EAST), Ltd. Hong Kong
www.technovitas.com