VEGA KS ( 1/2/3) KVA MANUAL
30
08
BYPASS enable/disable setting
Press Enter button
P
to change
thesetting(ON or OFF).
Press UP button ▲ to select the
previous setting.
Press DOWN button ▼ to save
and exit the setup.
3-4
Operating Mode Description
Mode
Description
Indicator
Line Mode
The green LED is on.
When input AC mains is in line with the
working conditions, UPS will work in line
mode,charge the battery and protect the load.
Battery
Mode
The battery yellow LED ison,and the buzzer
beeps once per 4 seconds.
When the mains power down or instable, UPS
will turn to Battery Mode at once. If the mains
recovers,the UPS will transfer to line mode.
If battery voltage low alarm activates, the
indicator of battery LED flashes. If battery
voltage reaches low limit, UPS will turn off to
protect the battery. UPS will auto-restart when
the mains recover.
NOTE
:The back up time of Battery Mode is
subject to the load and EBP numbers.