Jumper Options: 

 
 

The ICR-116 has two sets of Configuration Jumpers to accommodate various PLC Control Options . 
 
Both sides of the Relay Power Supply are connected to the ICR-116. When the Power Supply is 
connected properly, the Power Indication  should be lighted Green. 
 

 
CALL COMMON SELECT: 

 
CALL COMMON is connected to all Station Connectors - Pin 4 and Pin 3 of the Power Connector. 
The CALL COMMON  may be referenced to either Power Supply rail, allowed to float, or referenced to 
an external  “Common”. 
 
In most Installations,  the CALL COMMON  is referenced to the Relay Power Supply. For Convenience 
the Jumper may be in either Position: 
 

+24 VDC CALL COMMON is connected to the +24 VDC Relay Power Supply Rail 
-24 VDC CALL COMMON  is connected to the -24 VDC Relay Power Supply Rail 

 
If the CALL COMMON  Jumper is removed, the CALL COMMON  pin on the POWER Connector floats  
and may reference to any source. 
 

 
RELAY COMMON SELECT: 

 
The Relay SELECT-X lines may be reference to either Rail of the Relay Power Supply 
 

+24 VDC Sinking Drivers, Relay indicators will light Green when a relay is energized 
-24 VDC Sourcing Drivers, Relay indicators will light Red when a relay is energized 

 

 
NOTES: 
 

CALL COMMON is connected to CHASSIS  with a 1MEG-Ohm resistor  
-24 VDC is connected to CHASSIS  with another 1MEG-Ohm resistor 
The +24VDC has a 500MA  Resettable Fuse for the Relays 
The +24VDC has another 500MA  Resettable Fuse for the SELECT & CALL Connectors 

 
 