11
Step 7. Configure the settings for the temperature sensors and the room regulators
To enable EU L-8 external controller to control a given zone, it is necessary to provide it with current temperature value.
The easiest way is to use C-8r temperature sensor. If the user wants to be able to change the pre-set temperature value
directly from the zone, it is advisable to use R-8b, R-8z room regulators.
The user may also choose M-8 room regulator which offers additional functionalities apart from sending the current
temperature readings. It serves as a master controller enabling the user to change the pre-set zone temperatures, adjust
the local and global weekly schedules etc. Only one room regulator of this type may be installed in the heating system.
Regardless of the type of temperature sensor / room regulator chosen, it must be registered in a particular zone in EU L-8
controller menu.
NOTE
In some versions of room regulators there is no communication button at the back of the device - then you should
use PLUS button in the registration procedure. Only one regulator may be assigned to one zone.
The following rules must be kept in mind:
- The maximum of one temperature sensor may be assigned to each zone.
- Once registered, the sensor cannot be unregistered, but only switched off in the submenu of a given zone
- If the user attempts to assign a sensor to the zone to which other sensor has already been assigned, the first sensor becomes
unregistered and it is replaced by the second one
- If the user attempts to assign a sensor which has already been assigned to a different zone, the sensor is unregistered from
the first zone and registered in the new one
It is possible to set individual pre-set temperature value and weekly schedule for each room sensor assigned to a given zone.
The settings may be configured both in the controller menu and via www.emodul.eu (using ST-507 module or WIFI RS).
Communication
button in C-8r
room
temperature
sensor
Room temperature sensor C-8r, C-mini, M-8 - In order to
register, go to Registration in the submenu of a given zone
(Zones / Zone 1-8 / Room sensor / Registration) and press the
communication button on the sensor to register the sensor in
the controller.
If the process has been completed successfully, EU L-8
external controller display and the room regulator display will
show an appropriate message. Otherwise, the process must
be conducted again.