tech

2. Temperature control 

This   parameter   determines   the     sampling   (control)   frequency   of   the 

water temperature behind the valve for the CH or the HUW system. If the 
sensor indicates a change in temperature (deviation from the set value), then 
the electric valve will open or close by the set stroke in order to return to the 
set temperature. 

3. Opening time

In this  function the time of full opening  of the valve  is set, in other 

words, time in which the valve is open to the value of 100%. This time should 
be selected according to the owned valve servomotor (stated on the rating 
plate).

4. Unit step

In this function, per cent unit stroke of valve opening is set, namely 

which maximum opening or closing percent may each time be performed by 
the mixing valve (maximum valve movement in one measurement cycle).

5. Minimum opening

In this function, the minimum value of the valve opening is set. Below 

this value, the mixing valve will not close any further.

6. Valve type

With the use of this option, the user selects the type of the valve: CH or 

floor. 

7. Weather-based control

By means of this parameter, it is possible to adjust the temperature set 

for valve 1, for respective values of external temperatures. On the basis of 
agreed points, values for intermediate points are calculated.

TEMP. FOR -20
TEMP. FOR

 -10

TEMP. FOR

 0

TEMP. FOR

 10

A detailed description of this function is included in Chapter IV.s).

8. Return protection

This function permits setting the boiler protection against too cool water 

returning from the main circulation, which could cause low-temperature boiler 
corrosion.   The   return   protection   operates   in   the   way   that   when   the 
temperature is too low, valve is closed, until the short circulation of the boiler 
reaches the appropriate temperature. This function protects also the boiler 
against dangerously high temperature of return in order to prevent boiling of 
water.

After enabling this function, the user sets the minimum and maximum 

acceptable temperature of return:

9. Additional sensors

After   selecting   this   function,   the   user   has   the   possibility   of   selecting 

sensors from which the data on temperatures for the valve will be collected. 
Temperatures can be collected from module sensors (

own

) or according to the 

15

 -

Summary of Contents for ST-431

Page 1: ...tech 1...

Page 2: ...compliant with the Regulation by the Ministry of Economy Journal of Laws Dz U 155 Item 1089 of July 21 2007 implementing provisions of the Low Voltage Directive LVD 2006 95 EC of January 16 2007 The S...

Page 3: ...from the mains before working on the power supply cable connections device installation etc All connection works must only be carried out by qualified electricians Before activating the controller me...

Page 4: ...ST 431 user manual 4...

Page 5: ...water boiler II Principle of operation Description of the control panel The principle of operation of the controller to valve servomotor is based on mixing feed circulating warm water with water retu...

Page 6: ...button Any settings may be changed in a similar manner II a Main page During normal regulator operation graphic display shows the homepage on which the following are displayed Valve type CH Floor By...

Page 7: ...position dangerous see chapter III d for the circulation III c Screen view Using this function appearance of the homepage may be changed between the views of the basic valve the view of the sensors te...

Page 8: ...ption manual operation the user has the possibility of manually opening closing the valve and additional valves if active and switching on or off the pump for the purpose of inspection of the correct...

Page 9: ...e display shows the boiler manufacturer s logo along with software version of the regulator IV Installer menu IV a Summer mode In this mode the regulator closes CO valve so as not to heat house unnece...

Page 10: ...too high return temperature serves to prevent the hazardous growth in boiler temperature The user sets the maximum acceptable return temperature In the case of the hazardous growth in temperature the...

Page 11: ...reset temperature at the moment of achieving the preset temperature at the room regulator room heat up NOTE If in function Room regulator see IV e option Closing is set then function Reduction in room...

Page 12: ...larm If the maximum floor temperature is reached the boiler protection function is deactivated In this case the floor installation protection will have a higher priority IV i Opening direction If afte...

Page 13: ...reaching the temperature preset by the controller the symbol p room regulator heated up will be displayed permanently WEEKLY CONTROL the preset valve temperature depends on the deviations defined for...

Page 14: ...fragile floor installation IV o Valve 1 NOTE Controlling additional valve is possible after purchasing and connecting to the controller control module ST 61 which is not provided in the standard versi...

Page 15: ...pe of the valve CH or floor 7 Weather based control By means of this parameter it is possible to adjust the temperature set for valve 1 for respective values of external temperatures On the basis of a...

Page 16: ...ith primary controller mounted on the boiler If the communication mode is selected as subordinate the valve controller operates as a module and all its settings are made from the boiler controller IV...

Page 17: ...controller XA 20 C XB 10 C XC 0 C XD 10 C YA YB YC YD preset valve temperatures for respective external temperatures XA XB XC XD IV t Weekly control This function is used for programming daily temper...

Page 18: ...ous one specific hours and requested deviations from the temperature preset for business days Monday Friday and on weekend Saturday Sunday should be indicated Example Monday Friday set 300 AM TEMP 100...

Page 19: ...ning 2 Alarm VALVE SENSOR means an incorrect connection or lack of connection of the valve sensor or its damage It is a sensor strategic for valve operation therefore it should be replaced immediately...

Page 20: ...n max 4W Temperature endurance of the sensors 25o C 95o C Ambient temperature 5o C 50o C Load at each outlet 0 5A Fuse insert 1 6A ATTENTION In the case of the lack of flow in the short circulation of...

Page 21: ...tech Schematic diagram 21...

Page 22: ...mp anti stop 9 IV c Boiler sensor 10 IV c 1 Return protection 10 IV c 2 Boiler protection 10 IV c 3 Pump activation 10 IV d Temperature control 11 IV e Reduction in room control 11 IV f Room regulator...

Page 23: ...tech 23...

Page 24: ...tech 24...

Reviews: