tech
2. Temperature control
This parameter determines the sampling (control) frequency of the
water temperature behind the valve for the CH or the HUW system. If the
sensor indicates a change in temperature (deviation from the set value), then
the electric valve will open or close by the set stroke in order to return to the
set temperature.
3. Opening time
In this function the time of full opening of the valve is set, in other
words, time in which the valve is open to the value of 100%. This time should
be selected according to the owned valve servomotor (stated on the rating
plate).
4. Unit step
In this function, per cent unit stroke of valve opening is set, namely
which maximum opening or closing percent may each time be performed by
the mixing valve (maximum valve movement in one measurement cycle).
5. Minimum opening
In this function, the minimum value of the valve opening is set. Below
this value, the mixing valve will not close any further.
6. Valve type
With the use of this option, the user selects the type of the valve: CH or
floor.
7. Weather-based control
By means of this parameter, it is possible to adjust the temperature set
for valve 1, for respective values of external temperatures. On the basis of
agreed points, values for intermediate points are calculated.
TEMP. FOR -20
TEMP. FOR
-10
TEMP. FOR
0
TEMP. FOR
10
A detailed description of this function is included in Chapter IV.s).
8. Return protection
This function permits setting the boiler protection against too cool water
returning from the main circulation, which could cause low-temperature boiler
corrosion. The return protection operates in the way that when the
temperature is too low, valve is closed, until the short circulation of the boiler
reaches the appropriate temperature. This function protects also the boiler
against dangerously high temperature of return in order to prevent boiling of
water.
After enabling this function, the user sets the minimum and maximum
acceptable temperature of return:
9. Additional sensors
After selecting this function, the user has the possibility of selecting
sensors from which the data on temperatures for the valve will be collected.
Temperatures can be collected from module sensors (
own
) or according to the
-
15
-