Parallel Pumps
In this mode, the pumps run initially in parallel above the pump
activation threshold (set to 40°C by default). The central heating pump
continues to run and the hot consumption water pump is shut off after
the water heater setpoint temperature has been reached.
ATTENTION:
in this mode, you should mount a three-way valve or a
mixing valve that will maintain different temperatures in the water heater
and in the house.
II.9.d)
Summer Mode
When the function is enabled, the central heating pump is switched off
and the hot consumption water pump is activated above the pump
activation threshold (set to 40°C by default). In this mode, the hot
consumption water pump continues to run above the pump activation
threshold (set to 40°C by default). In the summer mode, the water
heater setpoint temperature is to be set. When the summer mode is
disabled, the actual temperature of the central heating and two
temperatures (actual and setpoint) of the hot consumption water are
displayed.
II.10.Sustain Mode Operation
With this function, you can set the operation time for the fuel feeder and
the fan.
-11-
SUMMER MODE
C.H. H.C.W.