User’s manual 

 
 

4.

 

Switch the UPS off (by pressing again the 

ON/OFF

 button for about 2 seconds). 

5.

 

Connect  the  devices  to  be  supplied  to  the  UPS  outputs,  by  using  only  the  included  cables.  Be  sure  all  the 
devices have the main switch in ON position. 

6.

 

Turn  on  the  UPS  again.  Check  that  it  starts  working  correctly  and  it  doesn’t  signal

 

any  sort  of  anomaly. 

Moreover be sure that all the devices connected to the UPS outputs are working correctly.  

7.

 

Simulate a black-out by removing the AC Input line. The UPS starts working in 

Battery mode

: the UPS emits 

an acoustic alarm signal every 4 seconds and simultaneously the 

LINE/BATTERY 

led flashes.  

8.

 

Be sure that all the devices connected to the UPS outputs are working correctly and the UPS doesn’t signal

 

any sort of anomaly. 

9.

 

Restore the AC Input line: after few seconds the UPS turns back in Normal mode. 

 

Before  using  ECO  normally,  leave  it  in  Normal  mode  in  order  to  charge  the  batteries  completely  as  specified  at 
point 3. The batteries reach the 90% of their capacity after about 4 hours of recharge. 

 

 

It is compulsory to ground/earth the UPS according to the Safety Standards. 

Risk  of  electric  shock  at  the  Output  lines  if  the  UPS  is  ON,  even  when  the  UPS  is  not 
connected to AC utility line. 

Risk  of  electric  shock  at  the  Output  lines  while  the  unit  is  connected  to  the  AC  utility 
line. 

Risk of electric shock: do not remove the cover. The UPS contains internal parts, which 
are at a high Voltage and are potentially dangerous, capable of causing injury or death 
by electric shock. 

There  are  no  internal  parts  in  the  UPS  that  are  user  serviceable.  Any  repair  or 
maintenance  work  must  be  performed  exclusively  by  qualified  technical  personnel 
authorized  by  TECNOWARE.  TECNOWARE  declines  any  responsibility  if  this  warning  is 
disregarded. 

Disregard for these warnings may lead to a risk of electric shock to operators. 

 
 

6

 

Functioning 

6.1

 

Normal Mode 

The UPS typically works in 

Normal mode

: Input mains power is available and its amplitude is within specifications.  

In Normal mode the 

LINE/BATTERY

 led is always on. 

During Normal mode, the UPS recharges the batteries and keeps them in an optimal charging voltage.   

Summary of Contents for ECO 0.50

Page 1: ...Uninterruptible Power Supply ECO 0 50 ECO 0 70 ECO 0 90 ECO 1 1 ECO 1 3 User s manual...

Page 2: ......

Page 3: ...8 Maintenance 10 8 1 UPS Cleaning 10 8 2 Battery 10 8 3 Battery Replacement 10 8 4 Operator Safety 11 9 Troubleshooting 12 Conformity to the European Directives 13 Product Disposal 13 Lead Batteries 1...

Page 4: ...the batteries they will remain powered and therefore dangerous even after the UPS has been disconnected from AC power mains Before any repair or maintenance work disconnect the batteries by removing t...

Page 5: ...ns for the operator for the UPS correct installation and gives useful advice on the product and battery maintenance For any type of problem please refer to this manual before calling the customer serv...

Page 6: ...signed to operate in a protected environment e g offices We therefore recommend installing it in a place with very little or no humidity dust or smoke In all circumstances see the Technical Characteri...

Page 7: ...there are see figure 1 1 The ON OFF button enables the user to turn ON OFF the UPS 2 The LINE BATTERY led this led blue color is always on during the functioning in Normal Mode it flashes one time eve...

Page 8: ...the UPS 2 Connect the UPS Input socket to the AC line outlet through the Personal Computer supplying cable It is mandatory to ground the AC line outlet according to the Safety Standards Carefully che...

Page 9: ...t point 3 The batteries reach the 90 of their capacity after about 4 hours of recharge It is compulsory to ground earth the UPS according to the Safety Standards Risk of electric shock at the Output l...

Page 10: ...ing the batteries from discharging excessively the UPS stops supplying Output power deactivates control panel indication and goes to a waiting state Once AC Input comes back on the UPS restarts automa...

Page 11: ...Single phase 230 Vac Output Voltage Regulation Normal mode As Input Output Voltage Regulation Battery mode 5 Output Inverter Waveform Modified Sinewave Accepted Overload 130 Certifications CE Standar...

Page 12: ...onth Take in mind that batteries are recharged automatically if the UPS works in Normal mode or if the UPS is off and connected to the AC Input Line Battery life strongly depends on the ambient temper...

Page 13: ...ay tools or metal parts on top of batteries e Disconnect the charging source prior to connecting or disconnecting battery terminals f Determine if battery is inadvertently grounded If inadvertently gr...

Page 14: ...remain powered and therefore dangerous even after the UPS has been disconnected from AC power mains Before any repair or maintenance work disconnect the batteries by removing the positive cable red c...

Page 15: ...urban waste but must be treated as a separate waste Any violation is indictable with financial sanctions as per in force regulations An incorrect waste disposal or an improper use of the same or of a...

Page 16: ...TECNOWARE s r l www tecnoware com...

Reviews: