eMiniFlush With Fault Output Setup Instructions  

 
1.  Ensure that the fault output link has been wired between the eMiniFlush and AC Power Board. (As 

shown below) 

 

 
 
 
 

 
 
 
 
 
 

 

 
 
 

 
Note

: The voltage free fault output is located on the bottom right of the AC Power Board. A Normally 

Closed and a Normally Open Contact is provided and can be connected either to a fault alert system or to 
stop a pump. 
 
When setup as per these instructions the dry contact coil will energize when a fault occurs. For example, 
in fault, the NC will open and the NO will close. Depending on the type of pump controller you have, you 
may need to use the NO or NC. If it’s a simple interruption of a pump contactor coil then NC should be 
used. 
 
2. Wire the filter flush solenoids between Output Common and Output 2, Output 3, Output 4, Output 5  

 
NOTE: Software output names and labels on circuit board are different. In software Output 1 is the 
Master Output on the board e.g. Software Output 1 = Circuit Board Output M and Software Output 
2 = Circuit Board Output 1 

and etc…). 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

Output Common 

Output 5 

– Filter Valve 4 

Output 4 

– Filter Valve 3 

Output 3 

– Filter Valve 2 

Output 1 

– Fault Output 

Output 2 

– Filter Valve 1 

Flush Valves

Valve
Power

DC Power
Supply

Digital Inputs

AC Power board 

eMiniFlush 
Controller  
Board 

Wiring required 
to enable 
voltage free 
output relay to 
operate. 