13
Last Flush XFlsh
XXXX min
Output Relay
Flushing
Press UP
once.
Up
Enter
Down
Input the maximum number of flushes per hour that you wish to allow. If this is exceeded then the
controller will display
"XFlsh”
indicating the set maximum flushes has been exceeded.
The
XFlsh
message does not stop flushing. The message will update every hour. To clear the
message press the "ENTER" key
Press UP
once.
Up
Enter
Down
The FILTER CONTROLLER has one programmable output that can be set to any one of the following
functions.
Program
Function
Description
Delay time
Flushing
Any filter flushing
1 sec
Any Fault
•
Filter blocked
DP Input continuously
on.
5 sec
Any Alarm
•
Excess Flush alarm
•
Excess flow alarm
5 sec
Excess flow
Excess flow alarm
trip
5 sec
Any Fault/Alarm
Any alarm or fault
as detailed above
5 sec
The Programmable output is a relay rated to 5 amps; as such the power supply fuse must not exceed
5 amps. Failure to fit the correct fuse may cause early failure or damage to this Filter Flusher.
Max Flushes / Hr
20