An alarm message will show on the main screen
showing that there is a low level shutdown fault.
The fault will also be recorded in the FAULT
HISTORY sub menu. To clear the fault and restart
the system press the ENTER key.
Note: All pumps will be shutdown including manual pumps (key pad control only).
If Low Limit Action is set to OFF the Low Limit and then the Low Levl Delay screens will
then display ------OFF---- and can be not altered.
Cut In Level
The Cut In Level is the level at which the system
will restart or the next pump will start. This Level must
be higher than the Low Level Shutdown. If the system is
re-starting, then the restart timer must have timed out before the first pump will start. If
there is a pump is already running, then the Cut In timer must have timed out before the
next pump will start. Pumps may also be prevented from starting if the Max starts per
hour setting has been exceeded.
A message will appear on the status screen letting you
know that it has occurred.
(This option is set in- Configuration -> Excess Run Protection. Note in Multilevel Mode
Cut In Level 1 / Cut In Level 2 etc will be displayed pending number of pumps selected)
Cut Out Level
The Cut Out Level is the level at which the system
will start to turn off pumps. This Level must
be lower than the Cut In Level. The Cut Out timer must
have timed out before the next pump will be turned off.
Pumps may also be prevented from stopping if the
Minimum run time for all pumps that are currently
running, and have not yet timed out.
(This option is set in- Configuration -> Excess Run Protection, Note in Multilevel Mode
Cut Out Level 1 / Cut Out Level 2 etc will be displayed pending number of pumps
selected)
High Level Shutdown
This is the alarm level point for High Level . If any pump is
running and the system rises above this Level and
remains there for the period of the “HiLevel Delay” time
the system will act according to the setting in the “High Limit Action” Sub menu.
➢
If High Limit Action is set to OFF, then no action is taken.
➢
If High Limit Action is set to Alarm, then an alarm is only logged.
➢
If High Limit Action is set to Shutdown, then a shutdown is initiated.
Cut In Level (1/2/3)
XXXX
LO LEVEL SHUTDWN
HiLevel Shutdown
XXXX
Cut Out Level
XXXX
PUMP/S REACHED
MAX Starts PerHr
Min Run Time ON
Pump Stop X Secs