www.techsys.com.au
Version 1.3 11/12/11
29
C o r p o r a t io n
CONFIGURE
CONFIGURE
Operating Mode
selection MultiLevel
Pressure, Flowrate,
Temperature, Single Level
Multi Level.
*Control Mode
Tank Empty
Tank Fill
Number of pumps
number
3
0 - 6
*Transducer Zero
unitless
0 - 9999
*Adjust Level
unitless
0 - 9999
*Averaging
number
20
0 - 50
Scale An Output
number
1000
Pump Flow Rate
per Min
5
1-9999 /Min
Auto Rotation
selection Full
Full, *Pump 1 - Pump 6,
Every 24 Hours, Low Hours.
LoLevel Restarts
selection 0
0 - 250
Sensing Input
selection Analogue
Analogue, Switched
Cycle Protection
selection Minimum Run Time
Minimum Run Time,
Max Starts PerHr
Low Limit Action
selection OFF
OFF, Alarm, Shutdown
HighLimit Action
selection OFF
OFF, Alarm, Shutdown
User Access Code
number
21
0 - 250
* "Transducer Zero", "Adjust Pressure" & "Averaging" are hidden when in "Switched" mode
* Pumps 2 - 6 are only visible if "Number of pumps" is set accordingly
* Pending Tank Fill or Tank Empty selection will reverse some logic . i.e Cut in level nowCut Out level etc
Operating Mode
Select the Control Parameter relevant to the operation.
The options are:
•
Pressure Control
•
Flowrate Control
•
Temperature Control
•
Single
Level Control
•
Mult
i Level Control
When the relevant selection is made the menu screens will change to reflect the control
parameters. This manual only covers the Level control option, therefore no other options
will be discussed.
Control Mode
Select the Control Parameter relevant to the operation.
The options are:
•
Tank Emptying
•
Tank Filling
Pending selection of the above will cause several settings to be reversed in mode of
operation or menu listing i.e. Cut In Level for tank empty now becomes Cut Out Level for
tank filling application etc.
Operating Mode
MultiLevel
Control Mode
Tank Emptying