TD20 Series VFD
Function Parameters
-43-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
voltage point 3 0.0%
–110.0% (rated motor voltage)
Setting range of P04.05: P04.03
– P04.07
Setting range of P04.07: P04.05
–P02.02 (rated motor
voltage frequency)
P04.09
V/F slip
compensation
gain
This function code is used to compensate the change of
the rotation speed caused by load during compensation
SVPWM control to improve the rigidity of the motor. It
can be set to the rated slip frequency of the motor which
is counted as below:
△
f=f
b
-n x p/60
Of which, f
b
is the rated frequency of the motor, its
function code is P02.02; n is the rated rotating speed of
the motor and its function code is P02.03; p is the pole
pair of the motor. 100.0% corresponds to the rated slip
frequency
△
f.
Setting range: 0.0
–200.0%
100.0%
○
P04.10
Low frequency
vibration
control factor
In the SVPWM control mode, current fluctuation may
occur to the motor on some frequency, especially the
motor with big power. The motor can not run stably or
overcurrent may occur. These phenomena can be
canceled by adjusting this parameter.
Setting range of P04.10: 0
–100
Setting range of P04.11: 0
–100
Setting range of P04.12: 0.00Hz
–P00.03 (the Max.
frequency)
10
○
P04.11
High
frequency
vibration
control factor
10
○
P04.12
Vibration
control
threshold
30.00
Hz
○
P04.26
Energy-saving
operation
selection
0: No operation
1: Automatic energy-saving operation
Motor on the light load conditions, automatically adjusts
the output voltage to save energy
0
◎
P04.27
Voltage
Setting
channel
Select the output setting channel at V/F curve
separation.
0: Keypad setting voltage: the output voltage is
determined by P04.28.
1: AI1 setting voltage
2: AI2 setting voltage
3: AI3 setting voltage
4: HDI setting voltage
5: Multi-step speed setting voltage;
0
○