Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.30
Frequency
decreasing
ratio in drop
control
The output frequency of the VFD changes as the load.
And it is mainly used to balance the power when several
VFDs drive one load.
Setting range: 0.00
–50.00Hz
0.00Hz
○
P08.32
FDT1
electrical level
detection
value
When the output frequency exceeds the corresponding
frequency of FDT electrical level, the multi-function
digital output terminals will output the signal of
"frequency level detect FDT" until the output frequency
decreases to a value lower than (FDT electrical
level
—FDT retention detection value) the corresponding
frequency, the signal is invalid. Below is the waveform
diagram:
Output frequency
FDT electrical level
FDT retention
Time
Time
Y, RO1, RO2
Setting range of P08.32: 0.00Hz
–P00.03
(the Max. frequency)
Setting range of P08.33 and P08.35: 0.0
–100.0%
Setting range of P08.34: 0.00Hz
–P00.03
(the Max. frequency)
60.00Hz
○
P08.33
FDT1
retention
detection
value
5.0%
○
P08.34
FDT2
electrical level
detection
value
60.00Hz
○
P08.35
FDT2
retention
detection
value
5.0%
○
P08.36
Frequency
arrival
detection
range
When the output frequency is among the below or above
range of the set frequency, the multi-function digital
output terminal will output the signal of "frequency
arrival", see the diagram below for detailed information:
Y
RO1, RO2
,
Output frequency
Set frequency
Detectionn range
Time
Time
The setting range: 0.00Hz
–P00.03 (the Max. frequency)
0.00Hz
○