TD20 Series VFD
Function Parameters
-68-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The cooling is better. The current of the stator other than
the rotor increases during magnetic flux braking, while
the cooling of the stator is more effective than the rotor.
P08.51
Current
adjustment
coefficient on
the input side
This function code is used to adjust the displayed
current of the AC input side.
Setting range: 0.00
–1.00
0.56
○
P09 Group PID control
P09.00
PID reference
source
When the frequency command selection (P00.06, P00.
07) is 7 or the voltage setting channel selection (P04.27)
is 6, the running mode of the VFD is procedure PID
controlled.
The parameter determines the target given channel
during the PID procures.
0: Keypad digital given (P09.01)
1: Analog channel AI1 given
2: Analog channel AI2 given
3: Analog channel AI3 set
4: High speed pulse HDI set
5: Multi-step speed set
6: MODBUS communication set
7
–9:Reserved
The setting target of procedure PID is a relative one,
100% of the setting equals to 100% of the response of
the controlled system.
The system is calculated according to the relative value
(0
–100.0%).
Note:
Multi-step speed given, it is realized by setting
P10 group parameters.
0
○
P09.01
Keypad PID
preset
When P09.00=0, set the parameter whose basic value is
the feedback value of the system.
The setting range:-100.0%
–100.0%
0.0%
○
P09.02
PID feedback
source
Select the PID channel by the parameter.
0: Analog channel AI1 feedback
1: Analog channel AI2 feedback
2: Analog channel AI3 feedback
3: High speed HDI feedback
4: MODBUS communication feedback
0
○
Summary of Contents for TD20 Series
Page 1: ......
Page 129: ...TD20 Series VFD Appendix C Peripheral Options and Parts 127 PB External brake resistor TD20...
Page 131: ......