TD20 Series VFD
Function Parameters
-75-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
After the users select the corresponding ACC/DEC time,
the combining 16 binary bit will change into decimal bit,
and then set the corresponding function codes.
Setting range: -0x0000
–0xFFFF
P10.36
PLC restart
mode
0: Restart from the first stage; stop during running
(cause by the stop command, fault or power loss), run
from the first stage after restart.
1: Continue to run from the stop frequency; stop during
running (cause by stop command and fault), the VFD will
record the running time automatically, enter into the
stage after restart and keep the remaining running at the
setting frequency.
0
◎
P10.37
Multi-step time
unit selection
0: Seconds; the running time of all stages is counted by
second
1: Minutes; the running time of all stages is counted by
minute
0
◎
P11 Group Protective parameters
P11.00
Phase loss
protection
0x00
–0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Output phase loss protection disable
1: Output phase loss protection enable
0x10
○
P11.01
Frequency-de
creasing at
sudden power
loss
0: Enabled
1: Disabled
0
○
P11.02
Frequency
decreasing
ratio at sudden
power loss
Setting range: 0.00Hz/s
–P00.03 (the Max. frequency)
After the power loss of the grid, the bus voltage drops to
the sudden frequency-decreasing point, the VFD begin
to decrease the running frequency at P11.02, to make
the VFD generate power again. The returning power can
maintain the bus voltage to ensure a rated running of the
VFD until the recovery of power.
Voltage degree
220V
460V
Frequency-decreasing
260V
530V
10.00
Hz/s
○