23
In this way, the system will work correctly and its performances will be optimized (few continuous cycles).
Fig. 8.6.1.1-1 - Collecting tank and 3-rods level sensor
Hints for rods cutting:
•
While cutting one rod, take care not to damage the isolation of the others.
•
Take-off 1cm of isolation tape from the end of each rod only after they have been cut to the
correct size.
•
The size of the rods has to be taken including the thread of the plastic connector cap they are
fixed in.
•
The rods are connected together passing through a blocking plate with three holes. This plate
needs to be repositioned and re-fixed according to the new size with PVC-sheath on each rod.
For the system supplied with 4-rods Level Probe, follow the same sizing procedure, as per the 3-rods Level Probe; and cut
the Absolute Max (alarm) rod in a way that its length is 1/3 of the tank total height (refer to
figure below).
Fig. 8.6.1.1-2 - Collecting tank and 4-rods level sensor